Where the CDU sits in the cooling chain
In a direct-to-chip deployment the heat path is: chip cold-plate → rack manifold → CDU → facility water. The CDU's job is to keep two loops separate. The primary (facility) loop brings comparatively warm, lower-quality chilled or condenser water from the plant. The secondary (technology / TCS) loop is a clean, filtered, temperature- and flow-controlled circuit feeding the cold plates. The CDU's heat exchanger transfers the load between them while the CDU's pumps, filter and controls protect the IT side. Get the CDU wrong and the rack throttles or trips; get it right and a 132 kW NVL72 stays in spec.
CDU types — what each is for
CDUs differ mainly by where they reject heat (liquid-to-liquid vs liquid-to-air) and where they physically sit (in a rack, in a row, beside a rack, or at room scale).
In-rack CDU
Mounts inside the 19″ rack it serves. Fast to deploy, isolates one rack/pod, no separate floor space. Capacity capped by rack U-height and the facility-water tap available at the cabinet.
In-row / row-based CDU
Stands in the row and feeds several racks via manifolds. The workhorse for dense AI halls — large heat exchanger, redundant pumps, big integrated filter. Needs facility chilled/condenser water piped to it.
Sidecar CDU
A slim cabinet attached to the side of a rack — between in-rack and in-row. Useful when in-rack U-space is full but a full row CDU is overkill, or for rear-door / single-cabinet retrofits.
Liquid-to-Air (L2A) CDU
Rejects the secondary-loop heat straight to room air via an internal air coil. The key retrofit enabler: lets you run direct-to-chip in a hall that has no chilled-water plumbing — at the cost of lower capacity and adding heat to the room.
Liquid-to-Liquid (L2L) CDU
Rejects to a facility water loop through a plate heat exchanger. Highest capacity and efficiency; the standard for purpose-built AI halls with a chilled- or condenser-water plant.
Facility / room-scale CDU
Large L2L units (e.g. 1.35–2.3 MW) that distribute to multiple rows/pods from a central location. Fewer units, central maintenance, but a bigger single-point footprint to design for redundancy (N+1 at the unit level).
In-row & facility-scale CDUs
Row-based and central L2L/L2A units, ordered by capacity. Specs cite the vendor product page; “approx.” marks family-level or rounded figures to confirm per configuration.
| Model | Capacity | Type | Secondary flow | dP / head | Approach | Footprint · weight | Fluid · filter · conn · BMS · class | Links |
|---|---|---|---|---|---|---|---|---|
| CoolChip CDU 2300 Vertiv |
2300 kW | L2L · row | not published | n/p | 4 °C | 2400×1200×1200 mm ~1793 kg wet |
water / PG-25 · 25–50 µm sec, 500 µm pri · 6″ sanitary · Modbus RTU+TCP · W45 | |
| Liebert XDU1350 Vertiv |
1368 kW (2912 max @ 8 °C) | L2L · row | 1200 L/min (2-pump) 1800 L/min (3-pump) | 2.44 bar | 4 °C | 2069×900×1243 mm ~650 kg |
water / glycol · 50 µm sec (triple-redundant), 500 µm pri · 4″ hygienic · Modbus + SNMP + CLI/web · W3 rated | |
| CHx2000 CoolIT Systems |
2000 kW | L2L · rack-mt | 2125 L/min @ 35 psi | ~2.4 bar | 5 °C | 750×1200 mm ftpt n/p |
PG-25 · 25 µm · 4″ tri-clamp · Redfish + SNMP/Modbus/BACnet · N+N hot-swap pumps | |
| CHx1500 CoolIT Systems |
1500 kW (1364 @ 4 °C) | L2L · rack-mt | 1800 L/min sec 2100 L/min pri | ~3.0 bar | 5 °C | n/p | PG · 25 µm (50 opt) · 4″ Victaulic · Redfish + SNMP/Modbus/BACnet · N+N hot-swap | |
| ROL4000 “Deschutes” Boyd (→ Eaton) |
2000 kW | L2L · 48U row | 1890 L/min (500 GPM) | up to 5.5 bar | 3 °C | 1651×1199×2364 mm ~3134 kg wet |
water / PG-25 · 0.2 µm side-stream · OCP UQD (est) · seal-less N+1 · OCP Deschutes | |
| MCDU-60 Motivair by Schneider |
2350 kW | L2L · floor | 1703 L/min (450 GPM) 800 GPM pri | 2.2 bar head | n/p | 2499×1600×1222 mm n/p |
25% PG · filter n/p · 6″ · BACnet/SNMP/Modbus · class n/p · 2 pumps (N+1) | |
| GoCool L2L 1500 Delta |
1500 kW (1016–1500) | L2L · floor | 1500 L/min (1650 max) 1300 L/min pri | n/p | 4–6 °C | 1200×1200×2300 mm 1900 kg wet |
fluid n/p · 50 µm · 4″ sanitary ferrule · SNMP/Modbus/BACnet · N+1 & N modes | |
| In-Row 2.4 MW (800 VDC) Delta |
2400 kW (2025 launch) | L2L · row | ~1.5 L/min/kW | n/p | ~4 °C | 1500×1200×2286 mm n/p |
Press-release figures (no datasheet yet) · 800 VDC pumps, N+1 | |
| RackChiller CDU800 nVent |
800 kW | L2L · floor | ≤1200 L/min/pump 950 L/min (N+N) | 2.7 bar sec | 4 K / 6 K | 800 (1200) ×2200 mm 1135 kg dry |
≤20% PG pri / ≤30% PG sec · 250 µm pri, 50 µm (25 opt) sec · 3″ tri-clamp · SNMP v3/Modbus · N+N VSD | |
| CyberCool CDU Stulz |
345–1380 kW | L2L · row | n/p | n/p | ~4 °C (FWS 32/TCS 36) | 600/900×1200×2090 mm n/p |
flexible fluid · 50 µm · sanitary quick-release · Modbus/BACnet/SNMP/HTTP · W32–W+ | |
| XCRow2000 Envicool |
2000 kW | L2L · row | 3000 L/min sec | n/p | n/p | 1200×2000×2200 mm n/p |
SoluKing PG25/EG25 · dual-pump backup | |
| Waterless EoR CDU ZutaCore 2-PHASE |
1200 / 2000 kW | 2-phase · EoR | <0.35 L/min/kW | n/p | n/p | n/p | dielectric refrigerant (R-1233zd class) · active-standby hot-swap · waterless / leak-safe in white space | |
| CoolChip CDU 70 Vertiv |
70 kW | L2A · row | 70 L/min | n/p | 15 °C | 2300×600×1200 mm 434 kg wet |
water / PG-25 · 50/25 µm · 6-fan N+1 · Modbus RTU+TCP · rejects to room air (no FWS) |
In-rack CDUs
Rack-integrated units (typically 3U–4U) for per-rack or small-pod deployments and faster retrofits. Includes single-phase water CDUs and two-phase (dielectric direct-to-chip / waterless) options — the 2-PHASE tag marks the latter.
| Model | Capacity | Form | Secondary flow | dP / head | Approach | Dimensions · weight | Fluid · filter · conn · BMS · class | Links |
|---|---|---|---|---|---|---|---|---|
| CHx200 CoolIT Systems |
200 kW | 4U in-rack | n/p | n/p | n/p | 4U · n/p | PG warm-water · N+1 pumps + N+1 PSU · 16 sensors / 4.3″ LCD · leak detect · W17–W+ | |
| CHx80 CoolIT Systems |
80 kW | 4U in-rack | n/p | n/p | n/p | 4U · n/p | PG warm-water · N+1 pumps + PSU · 4.3″ LCD + leak detect · ~100 servers / rack · W17–W+ | |
| RackChiller CHx CDU nVent Schroff |
200 kW+ @ 4 °C | 4U in-rack | 150 L/min | 2.76 bar (40 psi) sec | 4 °C | 430×950×177 mm 35 kg dry / 41 kg filled |
25% PG (OAT) sec, water pri · 100 µm · 1.5″ sanitary tri-clamp · dry-break QD · Webserver/Modbus/SNMP · W4 · 2 pumps N+1 (24 h alt) | |
| Neptune RM100 Lenovo |
100 kW | 4U L2L (bottom-of-rack) | ~87 L/min (HMI) | relief 3.5 bar | n/p (pri 4–11 °C) | 4U · n/p | sec DI+inhibitor or OAT PG-25, pri water ≤20% glycol · 50 µm sec · Ethernet/RS485/CAN · 2× 48 VDC pumps N+1 (7-day) · SP 18 °C dew-point reset | |
| In-Rack CDU Motivair (by Schneider) |
80–105 kW | 4U (top/bottom of 19″) | n/p | n/p | n/p | 483×178×813 mm ~38.6 kg |
water-glycol or dielectric · filter n/p · Modbus/BACnet/SNMP · redundant pumps (N+1) | |
| NeuCool IR150 Accelsius 2-PHASE |
150 kW | Rack-integrated (200 mm of an 800 mm enclosure, 42U IT) | n/p | n/p | n/p | 800 mm wide · 42U IT · n/p | R-1233zd(E) dielectric (R-515B planned) · 20 µm + PRV · iCDU N+1 hot-swap · SNMP/IPMI/Redfish/DCIM · W27 rated / W45 derated | |
| HyperCool In-Rack ZutaCore 2-PHASE |
20 – 120 kW (6U up to 100) | 19″ 3U / 6U | n/p | 3 bar refr / 4.5 bar water | n/p | 6U 440×1100×266 mm 90 kg dry (Water HRU) |
dielectric refrigerant (zero ODP, low GWP) · 8 L buffer · 1″ tri-clamp · RJ45 TCP/IP · W3 · N+1 pumps · 20 kW air variant = waterless |
Sizing & installation requirements
How to size a CDU to the rack heat load, the pipe it needs, and the physical install envelope. Figures marked OCP/ASHRAE are published; the rest are typical engineering values — confirm pressure drop and exact limits against the vendor data sheet and a qualified mechanical engineer. Full operating bands, water-quality acceptance criteria and the commissioning procedure live on the CDU Checklist.
1 · Flow & ΔT — the core sizing equation
A loop carries heat per the heat-balance Q = ṁ · cp · ΔT. Rearranged to volumetric flow for a 25% propylene-glycol secondary fluid (ρ ≈ 1.03 kg/L, cp ≈ 3.95 kJ/kg·K → cp,vol ≈ 4.07 kJ/L·K):
- At the OCP design point (ΔT ≈ 10 °C) this is ≈ 1.5 L/min per kW. OCP's published acceptable band is 1.25–2.0 L/min/kW for a 7.5–12 °C rise. (OCP cold-plate guidance.)
- Worked — rack: a 120 kW rack at 1.5 L/min/kW = 180 L/min through the secondary manifold.
- Worked — node: a 9 kW accelerator at 40 → 50 °C (ΔT 10) ≈ 13 L/min at the cold plate.
- Tighter ΔT → more flow (bigger pumps/pipe); wider ΔT → less flow but warmer return. Stay within the cold-plate's minimum per-chip flow (chip-vendor spec) and the CDU's dP window.
2 · Pipe sizing (secondary)
Size pipe for a velocity of ~1.5–3 m/s (too slow → fouling/air; too fast → erosion + high dP). Nominal diameters below are at ≈ 2 m/s — always re-check the actual pressure drop over the run.
| Secondary flow | ≈ Heat @ 1.5 LPM/kW | Bore @ ~2 m/s | Nominal |
|---|---|---|---|
| 50 L/min | ~33 kW | ~23 mm | DN25 (1″) |
| 100 L/min | ~67 kW | ~33 mm | DN32 (1¼″) |
| 180 L/min | ~120 kW | ~44 mm | DN40–50 (1½–2″) |
| 400 L/min | ~270 kW | ~65 mm | DN65 (2½″) |
| 1,500 L/min | ~1 MW | ~126 mm | DN125 (5″) |
| 3,000 L/min | ~2 MW | ~178 mm | DN200 (8″) |
3 · Heat exchanger & supply temperature (L2L)
- Approach (ATD) across the plate HX is typically ~3–5 °C — the secondary supply can't be colder than facility supply + ATD. Rising ATD over time = fouling.
- Facility supply temperature sets the achievable secondary temp and your free-cooling story — see the ASHRAE W-class table (W17/W27/W32/W40/W45/W+) on the checklist. Warmer classes (W40/W45) enable chiller-less / economiser operation.
- Hold secondary supply ≥ 2–3 °C above room dew point (the CDU's dew-point reset) to avoid condensation on cold plates and pipework.
4 · Physical install envelope — what to confirm
- Floor loading for the CDU's filled, operating weight + point load vs the raised-floor / slab rating.
- Service clearances front/rear/sides per the manual (door swing, tube routing, pump/filter pull-out space).
- Facility water (L2L) at the design flow/temp with isolation valves + strainer — or confirm the L2A room-air heat budget (the CRAH/CRAC must absorb the rejected heat).
- Dual power feeds (A/B) with correct breaker rating + earthing for the N+1 PSUs.
- BMS / leak-detection integration points (Modbus/BACnet/SNMP/Redfish) and leak-rope routing at base, manifolds and QDs.
- Redundancy — N+1 pumps + dual feeds sized so one pump/PSU can carry the full load.
Installation, operation & maintenance documentation hub
Manufacturer install guides and O&M manuals are usually delivered with the unit or through an authenticated support portal. Below are the publicly reachable vendor documentation entry points we could verify (HTTP 200) — open the portal and search the exact model for its install / operation / service manual. Login-gated PDFs are intentionally not deep-linked.
Governing standards & what this guide adds next
CDU selection, fluid spec and water quality follow published guidance. The deployment checklist and maintenance strategy (next ships) build on these.
ASHRAE TC 9.9 defines liquid-cooling water-temperature classes (W17 / W27 / W32 / W40 / W45 / W+ — the number is the maximum supply temperature in °C, with a 2 °C lower limit) and water-quality guidance. OCP adds practical cold-plate guidance (PG25 coolant, ~1.5 LPM/kW at a 10 °C rise, filtration and wetted-material compatibility).
Frequently asked questions
Short answers to the questions that come up most when choosing and deploying a CDU. Deeper detail and sources are on the checklist and deep comparison.