CDU Mini-BMS · Instrument view

Layout, P&ID & live parameters — per CDU type

A miniature building-management cockpit for liquid-cooling Coolant Distribution Units. Pick a CDU type to see where it sits in the datahall, how its piping & instrumentation is arranged, and a live (simulated) parameter feed. Inject a fault and watch the control logic respond — the same flow, pressure, temperature, pump-redundancy and leak signals a real CDU controller exposes to the BMS/DCIM.

DC SolutionsCDU Guide → Mini-BMS
CDU type
Scenario (fault injection)

Datahall installation layout — plan view

in-row

Live parameters (simulated)

P&ID schematic — piping & instrumentation

RUN
Educational simulation — not a live feed. Values are generated on-device from typical operating bands (see the CDU Checklist §01–§03 for the sourced parameter ranges, ASHRAE TC 9.9 W-classes and OCP cold-plate guidance). Parameter targets: secondary supply ~17–45 °C · ΔT ~8–12 °C · flow ~1.0–1.5 LPM/kW · dP ~0.5–3.0 bar · system pressure ~2–6 bar · pumps N+1 · leaks 0. Confirm exact set-points and alarm limits against the specific CDU's manufacturer manual. Not procurement, safety, or engineering advice.