Example A · In-Row normal
- Capacity = 300 kW.
- Specific flow = 1.30 LPM/kW.
- Total flow = 300 × 1.30 = 390 LPM.
- Return = 32 + 11 = 43°C.
- Loop dP 1.6 bar and pressure 4.0 bar sit inside their declared bands.
The engineering basis behind five CDU placement types, thirteen instrument tiles, six operating/fault scenarios, live trends, P&ID linkage and the guided fault walkthrough in cdu-mini-bms.html. All readings are local simulation values; manufacturer limits and commissioned cause/effect remain authoritative.
The mini-BMS teaches how a Coolant Distribution Unit separates facility and technology cooling loops, how instrument tags relate to operator tiles, and how one physical fault propagates across multiple readings. It is deliberately transparent: each displayed value comes from the selected type object, scenario delta and bounded deterministic waveform.
Values below are copied from the cockpit TYPES object. Capacity and placement captions are illustrative design/education inputs linked to the existing CDU toolkit.
| Type | Architecture / placement | Capacity | Supply | ΔT | Flow | Loop dP | System pressure |
|---|---|---|---|---|---|---|---|
| In-Rack | L2L; 3U–4U inside one rack | 80 kW | 30°C | 10 K | 1.30 LPM/kW | 1.2 bar | 3.5 bar |
| In-Row | L2L; cabinet between adjacent racks | 300 kW | 32°C | 11 K | 1.30 LPM/kW | 1.6 bar | 4.0 bar |
| Sidecar | L2L; slim unit beside a rack | 120 kW | 30°C | 9 K | 1.20 LPM/kW | 1.1 bar | 3.2 bar |
| L2L End-of-Row | Row CDU connected to facility CDW | 1,200 kW | 34°C | 12 K | 1.25 LPM/kW | 2.2 bar | 4.5 bar |
| L2A Air-Cooled | Liquid-to-air; room rejects the heat | 60 kW | 33°C | 9 K | 1.20 LPM/kW | 1.0 bar | 3.0 bar |
The current sample is the selected type baseline plus the active scenario delta plus a small sinusoidal display variation. The variation is not a random engineering basis and never changes type capacity or alarm bands.
compute(); FT-01Σ and TT-02 are explicitly labelled derived. cdu-mini-bms.html TYPES/TILES| Tag / tile | Meaning | Unit / normal band | Derivation / state |
|---|---|---|---|
| FT-01 Flow | Specific secondary flow | 1.0–1.5 LPM/kW | Type baseline + scenario delta. |
| FT-01Σ Flow total | Total secondary delivery | LPM | Specific flow × type capacity. |
| TT-01 Supply | Coolant supply to racks | 17–45°C | Type baseline + facility-water scenario delta. |
| TT-02 Return | Coolant return from racks | °C | Supply + ΔT. |
| ΔT-01 | Secondary temperature rise | 8–12 K | Type baseline + fault delta. |
| PDT-02 | Secondary loop differential pressure | 0.5–3.0 bar | Type baseline + restriction/flow delta. |
| PT-01 | Closed-loop system pressure | 2–6 bar | Type baseline; falls under leak. |
| LT-01 | Reservoir/expansion level | 45–70% | 56% nominal; falls 15 points under leak. |
| P-01 | Duty/standby pump state | N+1 ready | Pump A failure changes state to N, no standby. |
| PDT-01 | Filter condition | clean | Clog scenario raises filter dP and latches CLOG. |
| LSH-01 | Leak detection | DRY | Leak scenario latches ALARM. |
| TT-Δ | Heat-exchanger approach | 3–7 K | Not applicable to L2A; rises under hot facility water. |
| AT-01 | Coolant chemistry summary | PG25 in-spec | Static simulated state; not a lab measurement. |
Each scenario changes a coherent set of signals so the alarm tells a physical story rather than turning one isolated tile red.
| Scenario | Applied deltas / state | Expected alarm narrative | Operator learning action |
|---|---|---|---|
| Normal | No fault delta. | All parameters nominal; N+1 ready, loop dry. | Trace facility water → HX → pumps → filter → manifold → racks. |
| Leak | Leak=1; pressure −0.7 bar; level −15%; flow −0.06 LPM/kW. | LSH-01 alarm with falling LT-01/PT-01. | Acknowledge, isolate affected zone, locate, repair, pressure-test and refill. |
| Pump A fail | P-01A=0; flow −0.12; dP −0.18. | Warning: standby carries duty but N+1 is lost. | Keep cooling online and service the failed duty pump before another fault. |
| Filter clog | Loop dP +2.4 bar; filter CLOG; flow −0.4; ΔT +3.2 K. | PDT-01/PDT-02 alarm, falling flow, rising thermal rise. | Replace element at vendor threshold, then confirm recovered flow/dP. |
| Hot facility water | Supply +9°C; ΔT −2 K; HX approach +4 K. | Warning: warm TT-01 and widening TT-Δ. | Check facility CDW temperature/flow and HX fouling. |
| Low flow | Flow −0.6; ΔT +5 K; dP −0.5 bar. | FT-01 alarm with widening ΔT and lower pressure loss. | Check pump, valves, quick disconnects and trapped air. |
aria-pressed; P&ID instrument bubbles are keyboard focusable; Escape closes trend/link focus. Visual alarm color is always paired with NORMAL, WARN or ALARM text.TYPES, SCEN, TILES, trend and walkthrough implementation.| Term | Meaning | Limitation |
|---|---|---|
| CDU | Coolant Distribution Unit separating/controlling the technology cooling loop. | Actual architecture, fluids and controls are vendor/site specific. |
| L2L | Liquid-to-liquid heat rejection through a facility-water heat exchanger. | Facility supply/return and approach are not solved here. |
| L2A | Liquid-to-air heat rejection into the room. | Room CRAH/CRAC capacity is outside this model. |
| ΔT | Return temperature minus supply temperature. | Uniform loop value; no branch maldistribution model. |
| dP | Differential pressure across loop/filter elements. | No pump curve, valve Cv or hydraulic network solution. |
| N+1 | One standby pump beyond required duty. | Pump A failure changes to N; common-mode power/control risk is not modelled. |
| PG25 | Illustrative 25% propylene-glycol chemistry label. | No pH, conductivity or lab sample calculation; tile is simulated status only. |
Open gaps: vendor alarm set-points, fluid-property correction, pump/head selection, HX duty/approach solution, expansion sizing, controls fail-safe states, sensor accuracy, sampling/freshness and protocol integration. Those must be contracted before any live-controller claim.