OVHcloud SBG2 Strasbourg Data-Center Fire (10 March 2021)
In the early hours of 10 March 2021 a fire broke out in a ground-floor energy room at OVHcloud's SBG2 facility in Strasbourg, where the site's UPS units and their lead-acid battery banks were housed. Video surveillance and the fire panel traced the initiating event to a near-simultaneous electrical fault on UPS2 and its connected batteries. With no automatic suppression system in any of the five campus buildings, and a free-cooling design that used intumescent-treated raw-wood floors and single-skin cladding to aid airflow, the fire spread through the entire structure. De-energisation was slow because there was no accessible general site cut-off, forcing the grid operator to isolate an upstream substation; current was still present in the burning building well after the cut order. SBG2 was destroyed in its entirety, four of twelve rooms in adjacent SBG1 were partially destroyed, and the SBG2–SBG3 inter-building link was impacted. Roughly 30,000 servers were lost and about 3.6 million websites went offline. There were no casualties or injuries. French investigator BEA-RI could establish the fault location but not its precise cause, leaving several hypotheses open pending a court-expert examination.
Failure cascade
Trigger → primary fault → downstream blast radius, derived from the sourced root cause and affected-services record.
Facility & location
- Operator
- OVHcloud
- Data center
- SBG2 (Strasbourg campus)
- Location
- Strasbourg, France
- Date
- 2021-03-10
Impact & scale
- Users affected
- ~3.6 million websites taken offline; ~30,000 servers destroyed
- Financial
- Undetermined — total damages were still being assessed by a Strasbourg court-appointed expert panel at report time; no authoritative total was published
- Scope
- Catastrophic (total facility loss)
- Bare Metal dedicated servers
- Public Cloud instances
- VPS
- Hosted Private Cloud
- customer-hosted websites and databases
Impact data & metrics
| SBG2 lead-acid battery bank | ~800 batteries, ~30 kg each |
| Detection-to-safe-de-energisation gap | first alarm 00h35 -> site electrically secured ~02h30 (~1h55); full site dead only at 03h28 |
| On-site fire-water supply | single public hydrant, <60 m3/h; no owned reserve, no canal pumping |
| Fireboat EUROPA capacity | 3 pumps at 15,000 L/min + 2 foam/water lances at 4,500 L/min each |
| Foam concentrate consumed | ~4000 L |
| Personnel / casualties | night crew evacuated safely; 0 fatalities, 0 injuries |
| Building loss | SBG2 (6-level) total loss; SBG1 partially damaged (4 of 12 rooms per BEA-RI); SBG3/SBG4 intact |
| Customer impact | ~3.6 million websites and 464,000 domain names ceased responding on 10 Mar |
| SBG2 capacity | built 2016, capacity ~30,000 physical servers |
| Estimated damage | ~EUR105 million |
| Litigation (first-instance, later cut on appeal) | ~EUR250k combined to two customers in 2023 (EUR100k Bati Courtage; ~EUR145k Bluepad), reduced to a few hundred euros each on appeal under contractual caps; 130+ in class action |
| Fire duration | alarm 00h35 -> controlled ~06h45/07h00 -> extinguished ~10h02 (~9.5h) |
Magnitude profile
Extreme user and blast-radius impact — an entire data center destroyed with ~3.6M websites offline and ~30k servers lost, plus collateral damage to SBG1 and the SBG3 link. Financial score reflects a very large but formally unquantified loss (court-expert assessment still open). Duration score spans the ~9.5h fire fight and the multi-week service-restoration tail (recovery from 17 Mar; ~99% of key products re-delivered by 23 Apr).
Sequence of events (SOE)
- TRIGGER Ambient sensors on the rear of the SBG2 inverters log an anomalous humidity spike - later cited as supporting the liquid/humidity short-circuit hypothesis for ASI2.
- TRIGGER A further marked humidity rise is recorded just after 00h30, followed by continuous temperature increase on the inverters ahead of failure.
- DETECTION Near-simultaneous electrical faults strike the lead-acid batteries AND inverter ASI2 in two separate ground-floor energy rooms; first fire alarm reaches the site security PC. Optical and aspirating detectors 'ont parfaitement joue leur role'.
- DETECTION Security guard reaches ground-floor energy room no.2 and finds thick black smoke; aspirating detectors sense smoke on all floors within ~15 minutes.
- MITIGATION SBG2 evacuated; the small night crew is accounted for - zero victims, zero injuries.
- DETECTION OVH guard places the emergency call to the fire service (SIS/SDIS 67).
- MITIGATION Order given to cut electrical supply to the whole site - but no accessible general cut-off exists to execute it quickly.
- MITIGATION Firefighters arrive, observe 'des arcs electriques dans le local energie', deploy a single water lance while awaiting de-energisation, and judge the building design will not permit containment.
- MITIGATION SBG2 electrical supply cut by OVH.
- CASCADE Water applied at the SBG2 facade; backup energies of SBG3/SBG1/SBG4 cut by OVH; SBG2 first floor is fully involved less than an hour after the first alarm.
- CASCADE Whole first floor taken; upper-floor spread now unstoppable; two lances working (ground level plus an aerial ladder).
- MITIGATION Fireboat EUROPA requested because on-site water means are insufficient (single hydrant <60 m3/h).
- MITIGATION SER cuts remotely at the upstream source substation (client HT posts inside the fire zone could not be operated) - remote cut becomes effective.
- IMPACT Generalized flashover of SBG2; upper-floor temperature sensors saturate.
- IMPACT Current is STILL present in the fully-ablaze building 2 - residual lead-acid battery supply (~20 min) and auto-started diesel generators keep it live.
- MITIGATION Site judged electrically secured; massive water attack finally engaged - but SBG2 is fully involved and already spreading to SBG1 and SBG3.
- MITIGATION Fireboat EUROPA arrives, adding 3 pumps at 15,000 L/min and 2 foam/water lances at 4,500 L/min each - described as decisive in sparing SBG1/SBG3.
- CASCADE Fire spreads to SBG1 (container-type build, losing 4 of 12 rooms) and SBG3 (protected by a 2-hour firewall, though fire-stop doors were held open, degrading it).
- IMPACT 'A partir de 03h28, il n'y a plus de courant sur le site' - the site is finally fully dead.
- RECOVERY Fire declared 'maitrise' (under control).
- RECOVERY Fire extinguished; ~4000 L of foam concentrate consumed over the intervention.
- RESTORED SBG2 declared a total loss; all customer data and backups stored in SBG2 lost. Netcraft measured ~3.6 million websites / 464,000 domains ceasing to respond that morning.
- CASCADE A second fire breaks out in a battery room of SBG1 ('un nouvel incendie a lieu dans un local a batteries du batiment SBG1'), forcing a fresh site power-down and delaying recovery.
- RESTORED First-instance courts awarded ~EUR100k (Bati Courtage, Lille 26 Jan 2023) and ~EUR145k (Bluepad, 9 Mar 2023) - together ~EUR250k to two customers; both were drastically cut on appeal (2025-2026) under OVH's contractual liability caps (six months' fees). 130+ customers pursue a class action.
Root cause
Contributing factors
- No automatic fire-suppression system in ANY of the five SBG buildings (no sprinkler, water mist, or gas inerting) - a deliberate design choice per BEA-RI; the energy rooms had detection only, so the fire could not be attacked at its source. [BEA-RI report, via Wikipedia fr]
- Absence of a readily accessible general site electrical cut-off: isolation required tripping the upstream source substation because client-owned HT posts sat inside the fire zone and could not be operated, delaying safe de-energisation from the ~00h58 cut order to ~02h30. [BEA-RI report]
- MAINTENANCE / MONITORING GAP: the faulted inverter ASI2 had recurring, unexplained by-pass-mode trips and was serviced the very morning of the fire; the lead-acid batteries had NO scrutation/supervision, and OVH could not produce the inverters' operating parameters at the moment of failure. [BEA-RI report]
- Free-cooling building design - raw-wood floors with intumescent treatment, single-skin aluminium-blade cladding, high air permeability - let fire and smoke climb vertically extremely fast; aspirating detectors sensed smoke on all floors within ~15 minutes. [BEA-RI report, free-cooling airflow confirmed via Wikipedia fr]
- Grossly insufficient fire-water: a single public hydrant delivering under 60 m3/h, with no owned water reserve and no pumping means from the Rhine canal, forcing reliance on the fireboat EUROPA. [BEA-RI report]
- Diesel generators slaved to supply continuity auto-started despite the fire and had to be manually neutralized to keep them from restarting on the cut, prolonging the live-electrical condition. [BEA-RI report]
- Degraded passive protection: fire-stop doors were held open during evacuation, and the battery charge rooms did not meet the 2-hour fire resistance required under the 29/05/2000 arrete (rubric 2925). [BEA-RI report]
- UPS and its associated batteries were located in DIFFERENT rooms, and two near-simultaneous departures occurred across both spaces, complicating any single-point containment. [BEA-RI report]
- Customer-side resilience gap: many customers had no off-site/geo-redundant backup, so the SBG2 total loss destroyed both primary data and the only copies for those customers. [Wikipedia en]
Correction of errors (COE)
- Fit automatic fire-suppression to all energy/battery rooms and datahalls across the SBG estate and rebuild
- Provide accessible general electrical cut-off and separate UPS from associated batteries into fire-rated rooms
- Add UPS/battery supervision and operating-parameter logging; RCA recurring ASI by-pass trips before return-to-service
- Provision owned fire-water reserves/pumping sized to site (Rhine canal) beyond the single public hydrant
- Publish and complete the BEA-RI technical investigation and cooperate with judicial expertise on precise ignition cause
- Advise/enable customers on geo-redundant backups (default off-site backup offering)
Lessons learnt
- Fire detection without automatic suppression buys almost no containment time in a data center — SBG2 rooms had detection but no extinguishing system, and water could not be applied early without first cutting power.
- The battery-charging chain, not just the battery room, is the true hazard unit; the UPS and its batteries were in separate rooms and the fault spanned both, so single-room protection would not have prevented the fire.
- Energy-efficient free-cooling construction (combustible raw-wood floors, single-skin cladding) trades fire compartmentation for airflow — the same design that cuts cooling energy accelerated vertical fire spread.
- A facility must be de-energisable quickly and locally; relying on an upstream substation cut left the building live for over an hour, blocking safe massive water application while the fire grew.
- On-site water resilience matters — a single hydrant below 60 m3/h with no reserve and no canal-pumping capability forced dependence on an external fireboat that arrived roughly two hours into the incident.
- Preventive battery monitoring (operating conditions and state, per manufacturer rules, with BMS at scale) is essential observability; the exact fault cause could not be determined afterward.
- A total-loss fire is a plausible, not far-fetched, scenario for a data center and must be planned for by both operators and local emergency services.
Improvements & remediation
- Rebuild energy rooms and buildings with automatic fire suppression and proper fire-behaviour construction, incorporating SBG2 feedback into detection, firefighting means, and emergency procedures.
- Install an easily accessible general site cut-off and drill electrical-securing procedures so responders can safely deploy water within minutes rather than hours.
- Provide on-site extinguishing-water reserves and/or canal-pumping capability sized for a widespread-fire scenario, and ensure ICPE water-resource requirements are met.
- Treat the whole charging workshop (batteries plus charging equipment) as the regulated fire unit and design its compartmentation accordingly.
- Deploy battery monitoring / BMS with manufacturer-based preventive-maintenance and replacement rules across large battery fleets.
- Run a fleet-wide fire-vulnerability audit of all facilities and feed findings into rebuild standards.
- Advance professional fire-safety guides and ANSSI certification for data centers instead of ICPE classification, reflecting that the dominant consequence is economic/strategic (data loss and service unavailability) rather than human or environmental.
Comprehensive analysis
An ignition that was never fully explained - and did not need to be
BEA-RI is unusually candid that the precise mechanism of the near-simultaneous ASI2/battery faults was not established and was left to judicial expertise. The forensic weight therefore falls not on the spark but on why a spark in one ground-floor energy room became a total loss of a six-storey building and spread to two neighbours. The report's own hypotheses (cooling-system humidity, the same-morning maintenance, out-of-range inverter operation) are presented as candidates, not conclusions, and the equipment maker/model is deliberately unnamed. Any narrative that asserts a definitive electrical cause overstates the evidence.
The suppression void is the decisive finding
The single most consequential fact is that none of the five SBG buildings had any automatic fire suppression - a design choice, not an oversight. Detection performed flawlessly and saved every life, but detection without suppression only enables evacuation. With no sprinkler, mist or gas system, the only defence was hand extinguishers and the public water network, which was itself grossly undersized. This is the lever that would most plausibly have changed the outcome.
De-energisation as the true bottleneck
Even once firefighters were on scene, they could not commit water at scale because the building stayed live. No accessible general cut-off, client HT posts trapped inside the fire zone, generators auto-restarting on continuity logic, and ~20 minutes of residual lead-acid supply combined to keep current flowing until ~03h28. Flashover (~02h00) beat the safe-to-attack moment (~02h30). The electrical architecture, not firefighter effort, dictated the timeline.
Building physics engineered for cooling, not containment
Free-cooling drove the envelope design - high air permeability, ventilated single-skin cladding, raw-wood (intumescent-treated) floors - which is efficient thermally but carried smoke to every floor within ~15 minutes and gave fire a vertical chimney. Passive protection that should have compartmentalised (2-hour battery-room rating, fire-stop doors) was degraded in practice, with doors held open during evacuation. The same feature that made the DC efficient made it burn.
Blast radius and the limits of legal recourse
Netcraft measured ~3.6 million websites and 464,000 domains dropping offline; customers who relied solely on SBG2, including in-facility backups, lost data outright. Yet the litigation arc is a cautionary tale: first-instance awards of ~EUR100k and ~EUR145k to two customers in 2023 were largely gutted on appeal (2025-2026) under OVH's contractual liability caps, leaving token sums. The practical lesson for customers was self-provisioned geo-redundancy, because neither the facility nor the contract would make them whole.
Technical deep-dive
References & provenance
- regulatory BEA-RI - Rapport d'enquete technique, incendie d'un centre de donnees le 10 mars 2021 a Strasbourg (published 27 May 2022)“il n'y avait pas de systeme d'extinction automatise sur SBG2 (report finding as relayed by Wikipedia fr; primary PDF host unreachable this pass)”https://www.bea-ri.developpement-durable.gouv.fr/incendie-d-un-centre-de-donnees-le-10-mars-2021-a-a115.html
- official-postmortem BEA-RI — Rapport d'enquête sur l'incendie au sein du stockage de données OVH situé à Strasbourg (67) le 10 mars 2021 (N° MTE-BEARI-2022-005)“L'incendie a pris naissance au sein des locaux qui abritent les batteries et les ASI (alimentation sans interruption) nécessaires au fonctionnement des serveurs.”https://www.igedd.developpement-durable.gouv.fr/IMG/pdf/rapport_ovh_67_vdif_cle01cf13.pdf
- regulatory BEA-RI — French government technical investigation report on the OVH Strasbourg fire“The fire started in the premises which house the batteries and the UPS ... equipped with fire detection but had no automatic extinguishing system.”https://regmedia.co.uk/2022/06/10/ovh_report.pdf
- press OVHcloud - Wikipedia (English), 2021 Strasbourg fire section“was ordered to pay 250,000 EUR to two customers that had lost data, and more than 130 other customers are engaged in a class-action lawsuit against the company”https://en.wikipedia.org/wiki/OVHcloud
- press Incendie du centre de donnees d'OVHcloud a Strasbourg - Wikipedia (French)“un nouvel incendie a lieu dans un local a batteries du batiment SBG1”https://fr.wikipedia.org/wiki/Incendie_du_centre_de_donn%C3%A9es_d%27OVHcloud_%C3%A0_Strasbourg
- other Learning from the OVHcloud data center fire — Uptime Institute“The disaster started on the ground floor of the SBG2 building and quickly spread to the whole building.”https://journal.uptimeinstitute.com/learning-from-the-ovhcloud-data-center-fire/
- news The OVHcloud fire still smolders — Data Center Dynamics“OVH has chosen not to equip any of the five buildings in its Strasbourg data center with an automatic fire protection system.”https://www.datacenterdynamics.com/en/analysis/ovhcloud-fire-france-data-center/
- vendor Information on the Strasbourg site — OVHcloud newsroom“the production rate at our Croix site was increased from 1,500 servers per week to more than 3,000.”https://corporate.ovhcloud.com/en/newsroom/news/informations-site-strasbourg/
Sourced from public post-incident reports. Quotes are short attributed excerpts for provenance only; the analysis above is original and substantially shorter than its sources. Last verified 2026-07-31.