Incident dossier · Rank #41

Digital Realty Singapore Lithium-Ion UPS Fire (2024)

Digital Realty 2024-09-01 10h 0m core impact FirePower

A lithium-ion UPS battery fire at a Singapore data center forced an emergency power shutdown, disrupting customers including Alibaba and Lazada — another instance of Li-ion UPS risk in modern facilities.

Failure cascade

Failure cascade: trigger → fault → downstream impactTriggerPrimary faultDownstream impactTrigger — Fire (2024-09-01)Trigger · Fire2024-09-012024-09-01Primary fault at Digital Realty — Digital Realty Singapore data centerDigital RealtyDigital Realty Singapore data centerDigital Realty Singapore dataDownstream service degraded by the fault: Alibaba/Lazada regional services (reported)Alibaba/Lazada regional servicesDownstream service degraded by the fault: Colocation customersColocation customers

Trigger → primary fault → downstream blast radius, derived from the sourced root cause and affected-services record.

Facility & location

Operator
Digital Realty
Data center
Digital Realty Singapore data center
Location
Singapore, Singapore
Date
2024-09-01

Impact & scale

Users affected
Cloud/e-commerce customers incl. Alibaba/Lazada in the region
Financial
Not published
Scope
Li-ion UPS fire, emergency power-off
Services / systems down
  • Alibaba/Lazada regional services (reported)
  • Colocation customers

Impact data & metrics

Fire date10 Sep 2024 (morning SGT)
Occupants self-evacuated before firefighters arrived~20 people
Injuries0 (all personnel out by ~08:15 SGT)
SCDF water jets deployed4 water jets
Unmanned firefighting robots deployed1 (damping-down phase)
Alarm to emergency power shutdown~18 hours (DCD reconstruction; ~01:46, 11 Sep)
Total operation duration to 'stable'~10 Sep to 12 Sep (~2 days)
Facility~17,000 sqm, 4 stories, launched 2016
Battery-room location vs 2020 SCDF ESS standard3rd-floor mezzanine vs required ground floor
Tenants/services disruptedAlibaba Cloud Singapore AZ-C, Lazada, ByteDance/TikTok

Magnitude profile

Magnitude sub-scores (0–10)Magnitude sub-scores (0–10)Users 5Users affected (0–10) — breadth of the user/customer population impacted. — scored 5/10.Financial 4Financial impact (0–10) — direct + consequential cost. — scored 4/10.Duration 4Outage duration (0–10) — how long service was degraded/down. — scored 4/10.Blast 5Blast radius (0–10) — how wide the fault propagated across systems/regions. — scored 5/10.
Magnitude 4.6 = blast 5×0.35 + users 5×0.25 + financial 4×0.20 + duration 4×0.20 (sub-scores 0–10 · weighted composite)

Li-ion UPS fire forced emergency power shutdown, impacting customers incl. Alibaba/Lazada — sub-scores ESTIMATED from public impact reporting, pending deep research.

Sequence of events (SOE)

Phased sequence of events2024-09-10 morning SGT · TRIGGER — Electrical fault in a third-floor mezzanine battery room initiates Li-ion thermal runaway at the Digital Realty Digital Loyang data center, Loyang, Singapore. 'Early investigations suggest an electrical issue in one of the battery rooms triggered the blaze.'TRIGGER2024-09-10 morning SG2024-09-10 morning SGT · DETECTION — Building fire-alarm system activates — the first publicly indicated detection event; no discrete smoke/heat-sensor timing is disclosed beyond this alarm.DETECTION2024-09-10 morning SG2024-09-10 morning SGT · MITIGATION — Facility sprinkler systems activate over the involved battery/power rooms on the third-floor mezzanine.MITIGATION2024-09-10 morning SG2024-09-10 before arrival · MITIGATION — About 20 occupants self-evacuate the building before firefighters arrive.MITIGATION2024-09-10 befor2024-09-10 morning SGT · MITIGATION — SCDF alerted and responds to the Loyang data centre to secure the premises and stabilise the situation.MITIGATION2024-09-10 morning SG2024-09-10 ~08:15 SGT · MITIGATION — All on-site personnel evacuated with no injuries; SCDF deploys four water jets to cool and contain the battery fire.MITIGATION2024-09-10 ~08:15 SG2024-09-10 daytime · IMPACT — Alibaba Cloud detects network anomalies in Singapore Availability Zone C; Lazada and ByteDance/TikTok begin experiencing service disruption.IMPACT2024-09-10 dayti2024-09-10 daytime · CASCADE — Alibaba warns of increasing likelihood of a complete network outage in Availability Zone C if battery-room temperatures are not controlled; O&M engineers are unable to enter the building.CASCADE2024-09-10 dayti2024-09-10 evening SGT · MITIGATION — SCDF firefighting knocks down / contains the blaze after roughly half a day of cooling; operation flagged as prolonged due to battery cooling requirements (exact containment time per DCD reconstruction, not re-verified this pass).MITIGATION2024-09-10 evening SG2024-09-10 overnight to 2024-09-11 · IMPACT — Firefighting and sprinkler water accumulates and leaks into server halls; Alibaba reports 'water accumulation and leaks, posing a risk of electrical short circuits.'IMPACT2024-09-10 overn2024-09-11 early hours SGT · CASCADE — Emergency power shutdown of the affected building executed to prevent electrical short circuits from standing water — this de-energisation, not flame, takes Alibaba Cloud Availability Zone C fully offline (~01:46 per DCD, not re-verified this pass).CASCADE2024-09-11 early hours SG2024-09-11 second day · MITIGATION — Operation spills into a second day; an unmanned firefighting robot is deployed for damping-down as manual entry remains too hazardous/hot.MITIGATION2024-09-11 secon2024-09-12 · RECOVERY — SCDF declares the site stable after multi-day cooling and damping-down operations.RECOVERY2024-09-12post-fire (Sep 2024) · RECOVERY — BCA assesses the structure: minor plaster delamination, paint peeling and soot only, structural integrity intact; issues closure orders for portions of the third, fourth floors and mezzanine.RECOVERYpost-fire (Sep 2post-stabilisation (Sep 2024) · RESTORED — Alibaba carefully dries water-exposed hardware to ensure data security; migration and restoration of affected machinery proceeds as planned.RESTOREDpost-stabilisati

Root cause

Ignition source: the facility's lithium-ion battery bank serving the UPS/energy-storage backup of Digital Realty's Digital Loyang data center in Loyang, Singapore, housed in battery rooms on the third-floor mezzanine of the four-storey building. Press relaying SCDF reported the fire "involved lithium-ion batteries housed in battery rooms on the third floor." Proximate mechanism: thermal runaway initiated by an electrical fault — "Early investigations suggest an electrical issue in one of the battery rooms triggered the blaze" (Straits Times/SCDF). Once initiated, cell-to-cell thermal-runaway propagation — the self-sustaining, re-igniting behaviour characteristic of Li-ion cells — resisted extinguishment and forced prolonged cooling that spilled into a second day. DISCLOSED UNCERTAINTY: The public record does not disclose the battery/UPS make and model, the cell chemistry (NMC vs LFP), cell age, state of charge, or the precise electrical fault (internal cell short vs charger/BMS fault vs connection arc). No make/model/chemistry can be attributed without over-claiming. The specific Digital Realty site code and exact street address are not independently confirmed in this review pass and are therefore not asserted. LATENT ROOT — DESIGN/SITING, NOT A MAINTENANCE VIOLATION: The salient systemic root is battery-room placement. SCDF's 2020 safety standards require Energy Storage Systems (Li-ion battery rooms) to sit on the ground floor, but the failed batteries were on the third-floor mezzanine. Digital Realty's position is that the facility launched in 2016, before the 2020 standard, so the elevated placement predated and was not governed by that rule — a legacy/grandfathered design rather than a rules breach (DCD). This above-grade siting materially worsened the event: it complicated firefighter access and battery cooling, and it placed burning batteries within the same structure as live server halls, so suppression water drained down into the IT space and forced an emergency power shutdown. No public evidence identifies a maintenance, inspection, testing, hot-work, or deferred-work lapse as the ignition cause; the trigger is described only as "an electrical issue in one of the battery rooms." The dominant redundancy/design gap is therefore the co-location of an above-grade Li-ion energy-storage hazard above critical IT load, with water-based suppression as the only viable firefighting medium.

Contributing factors

Correction of errors (COE)

Lessons learnt

Improvements & remediation

Comprehensive analysis

A thermal-runaway fire, but a water-caused outage

The September 2024 fire at Digital Realty's Digital Loyang facility is best understood as two coupled events. The first was a lithium-ion battery fire on the third-floor mezzanine, triggered by an electrical fault and sustained by cell-to-cell thermal runaway that water can cool but not extinguish. The second — and the one that actually caused the customer-visible outage — was hydraulic: accumulated sprinkler and firefighting water draining down into server halls, forcing an emergency power shutdown to avoid short circuits. Flame never breached the IT space or structural integrity; the suppressant did the damage.

Above-grade battery siting as the systemic root

The decisive design condition was that an energy-storage hazard sat above live server halls with no water-tight separation. SCDF's 2020 ESS standard requires Li-ion battery rooms on the ground floor precisely to avoid this geometry; the failed rooms were on the third-floor mezzanine. Gravity did the rest — water migrated down onto energised equipment. Ground-floor siting with bunded, drained containment would have decoupled the battery event from the IT load.

Legacy compliance versus safe design

Digital Realty's stated position is that the facility launched in 2016, before the 2020 standard, so the elevated placement was grandfathered rather than a breach. That is legally coherent but operationally cautionary: the arrangement that was permissible under the older code is exactly the arrangement that turned a contained battery fire into a regional cloud outage. Grandfathered compliance is not evidence of safe design.

The multi-tenant cascade

Because a single building hosted Alibaba Cloud Singapore Availability Zone C, the emergency de-energisation propagated outward — first to Alibaba's own AZ-C, then to downstream tenants Lazada and ByteDance/TikTok. The blast radius demonstrates that logical availability-zone labels do not guarantee physical isolation when redundancy is concentrated in one structure. Recovery was further slowed by fire-safety protocol barring O&M engineers from re-entry until the site was declared stable.

Evidentiary gaps that remain open

The public record does not disclose the battery/UPS make and model, cell chemistry, age, state of charge, or the precise electrical fault. The trigger is described only as 'an electrical issue in one of the battery rooms.' No maintenance, inspection or hot-work lapse is identified — which is an absence of evidence, not a clean bill. A full root cause would require the undisclosed SCDF/Digital Realty investigation findings, which were not public as of this review.

Technical deep-dive

The event is a textbook illustration of why Li-ion energy storage co-located with IT load creates a cascading, water-coupled failure mode rather than a contained electrical fire. On the morning of 10 Sep 2024 the building fire-alarm system triggered — the first publicly indicated detection event; no discrete smoke/heat-sensor timing is disclosed beyond the alarm. Facility sprinklers activated and SCDF deployed four water jets on arrival. Crucially, water is a coolant, not an extinguishant, for Li-ion thermal runaway: it cannot arrest cell-to-cell propagation, only remove heat, so the fire re-asserted itself and the operation became a prolonged cooling exercise — contained the same day but requiring damping-down with an unmanned firefighting robot (conditions too hot/hazardous for manual entry) and not declared stable until 12 Sep. The decisive engineering failure was hydraulic, not thermal. Because the battery rooms sat on the third-floor mezzanine directly within the four-storey structure, accumulated firefighting and sprinkler water migrated downward into server halls. Alibaba reported the server room "started to experience water accumulation and leaks, posing a risk of electrical short circuits." To prevent energised electronics from short-circuiting in standing water, an emergency power shutdown of the affected building was executed in the early hours of 11 Sep — roughly 18 hours after the alarm per DCD's reconstruction of Alibaba's timeline. This de-energisation, not flame, is what took Alibaba Cloud Singapore Availability Zone C fully offline and cascaded to Lazada and ByteDance/TikTok. The fire itself never breached structural integrity: BCA found only minor plaster delamination, paint peeling and soot, and issued closure orders for portions of the third, fourth and mezzanine levels. Recovery was throttled by fire-safety protocol — Alibaba's O&M engineers were barred from re-entering the building — so wet hardware had to be carefully dried before migration/restoration. The lesson embedded in the physics: with an above-grade Li-ion hazard and water-only suppression, the suppressant becomes the primary agent of collateral IT damage.

References & provenance

Sourced from public post-incident reports. Quotes are short attributed excerpts for provenance only; the analysis above is original and substantially shorter than its sources. Last verified 2026-08-02 (seed — pending deep research).