← All incidents
Incident dossier · Rank #29 · magnitude 6.5

CyrusOne Aurora Cooling Failure Halts CME Group Trading (November 2025)

CyrusOne (tenant: CME Group) 2025-11-27 11h 0m to substantial restoration CoolingHuman error

Summary

A human-error cooling-tower switchover during a cold-weather changeover triggered a chiller-plant failure and temperatures above 100°F at CyrusOne's Aurora facility, halting CME Group's global futures and options trading for more than ten hours.

Users affected
Global derivatives market participants; CME futures/options across equities, rates, FX, commodities
Duration
11h 0m — Chiller failure evening 27 Nov CT → CME markets fully reopened ~08:30 ET 28 Nov (reported ~11 h)
Financial
Market-wide trading halt; direct loss not published
Scope
Sev-1 facility cooling loss (>10h trading halt)
Site
CyrusOne Aurora (Chicago-area) · Aurora, Illinois, United States
Services down
CME Globex futures/options trading, Market data feeds

How the defences failed

How the defences failed — CyrusOne5 failure modes in the order the sequence of events first shows them, 1 latent conditions with no moment in the record, ending in the outcome: CME markets halted ~11 h.LATENT — IN PLACE BEFORE THE EVENTFM-02 · RPN 324No contractor-boundary checksS9 · O4 · D9ACTIVE — IN THE ORDER THE RECORD SHOWS THEMFM-01 · RPN 432Freeze-prep steps skippedS9 · O6 · D8FM-03 · RPN 320Plant trips, no backup carriesS8 · O5 · D8FM-04 · RPN 120Alarms not tied to load-shedS5 · O4 · D6FM-06 · RPN 243Matching engines on one campusS9 · O3 · D9FM-05 · RPN 360Manual chiller restartS8 · O5 · D9OUTCOMECME markets halted ~11 hLEGENDHigh priorityMedium or low priorityNext failure in the record
How the defences failed — CyrusOne5 failure modes in the order the sequence of events first shows them, 1 latent conditions with no moment in the record, ending in the outcome: CME markets halted ~11 h.LATENT — BEFORE THE EVENTFM-02 · RPN 324No contractor-boundary checksS9 · O4 · D9ACTIVE — RECORD ORDERFM-01 · RPN 432Freeze-prep steps skippedS9 · O6 · D8FM-03 · RPN 320Plant trips, no backup carriesS8 · O5 · D8FM-04 · RPN 120Alarms not tied to load-shedS5 · O4 · D6FM-06 · RPN 243Matching engines on one campusS9 · O3 · D9FM-05 · RPN 360Manual chiller restartS8 · O5 · D9OUTCOMECME markets halted ~11 hLEGENDHigh priorityMedium or low priorityNext failure in the record
Every failure mode of the FMEA below. Active modes run in the order the sequence of events first shows them — record order, not a proof of cause; latent modes were in place before the event. Red outline: high priority. Dashed: no published corrective action.
Magnitude sub-scores (0–10)Magnitude sub-scores (0–10)Users 6Users affected (0–10) — breadth of the user/customer population impacted. — scored 6/10.Financial 8Financial impact (0–10) — direct + consequential cost. — scored 8/10.Duration 5Outage duration (0–10), from the measured duration by fixed bands: <1 h 3 · 1–4 h 4 · 4–12 h 5 · 12–24 h 6 · 1–3 d 7 · 3–7 d 8 · 7–30 d 9 · >30 d 10; no customer downtime 1. — scored 5/10.Blast 7Blast radius (0–10) — how wide the fault propagated across systems/regions. — scored 7/10.
Magnitude 6.5 = blast 7×0.35 + users 6×0.25 + financial 8×0.20 + duration 5×0.20 (sub-scores 0–10 · weighted composite)

Global futures/options market halt >10h from a cooling-plant failure — sub-scores ESTIMATED from public impact reporting, pending deep research.

All 9 impact metrics
Total outage duration~11 hours (reported 'over 11 hours')
Cooling units affected'multiple cooling units' (common-mode; exact count not disclosed)
Aurora campus IT capacity109 MW across 3 data centers, 450,000 sq ft
Corrective capacity added'additional redundancy to the cooling systems' (tonnage not disclosed)
Peak data-hall temperature (reported)>100degF (UNVERIFIED - not disclosed by CyrusOne; from a secondary incident summary)
EBS markets resume time~07:00 ET, 2025-11-28 (not independently reconfirmed)
Full market reopen time~08:30 ET, 2025-11-28 (not independently reconfirmed)
Aurora sale-leaseback (2016)~$130 million, 15-year term (UNVERIFIED facility-profile detail)
Financial falloutCyrusOne reportedly postponed/halted a bond sale after the failure

Sequence of events

  1. TRIGGER On the live approach to a hard freeze in the Chicago suburbs (Thanksgiving-window reopen), onsite staff and contractors began preparing/draining CHI1's cooling towers for freezing weather but failed to follow standard procedures for the winterization changeover (CyrusOne, confirmed to Bloomberg).Mechanical / cooling engineer
  2. CASCADE The procedural lapse induced a chiller-plant failure: CHI1 'experienced a chiller plant failure affecting multiple cooling units' - a common-mode trip taking more than one unit offline at once.
  3. CASCADE Chilled-water circulation to the data halls was lost; against ~109MW of IT capacity with low thermal mass, rack-inlet/room temperatures began climbing (a widely-cited summary reports >100degF; not disclosed by CyrusOne).
  4. DETECTION Thermal detection (not fire): plant/building monitoring (BMS/DCIM) and rising room/rack temperatures would have driven high-temperature alarms as the chiller plant failed. No accessible source states the exact minute the high-temp threshold tripped.
  5. MITIGATION Protective compute shutdown: to stop generating heat and protect hardware, CME's trading systems (Globex and related markets) were halted/failed over - an 'evacuation of compute' rather than any occupant evacuation (unmanned mechanical failure, no life-safety event).Customer
  6. IMPACT Global markets knocked out: the halt prevented traders from accessing futures prices for commodities and stocks across CME Group's derivatives markets (specific benchmark list per trade reporting: S&P 500, Nasdaq, Treasuries, WTI, gold, Nikkei, palm oil - not independently reconfirmed).
  7. MITIGATION CME issued a public notice that its markets were halted due to a cooling issue at the CyrusOne data center and that it was working to resolve the issue (exact wording attributed to trade reporting, not independently reconfirmed).Communications lead
  8. MITIGATION Emergency MECHANICAL response (no fire department / 911): CyrusOne mobilized engineering teams and contractors on-site to restart chillers and reconstitute chilled-water circulation.Mechanical / cooling engineer
  9. MITIGATION No suppression discharge occurred or was needed (no fire); the 'suppression analogue' - the cooling plant - had failed. Redundancy/backup cooling did not carry the load, forcing an orderly thermal de-rating/shutdown of IT.
  10. RECOVERY Chillers restarted at limited capacity and cooling reconstituted to rebuild chilled-water circulation to a stable state (any 'temporary/supplemental chillers and pipework' detail is attributed to DC Pulse and is unverified).
  11. RECOVERY EBS markets resumed trading as chilled-water circulation stabilized enough to bring IT load back safely (resume time per CNBC; not independently reconfirmed).
  12. RESTORED Stock futures and options trading fully reopened; CME reported all its markets were open and trading (per CNBC; not independently reconfirmed).
  13. RESTORED Trading in FX, stock and bond futures had resumed after being knocked out for roughly/over 11 hours; regulators (CFTC and SEC) reportedly aware and monitoring (per Reuters; not independently reconfirmed).Authority / investigator
  14. RECOVERY CyrusOne reported it had 'restored stable and secure operations at its Chicago 1 (CHI1) data center in Aurora, Illinois' and 'installed additional redundancy to the cooling systems.'Service recovery lead
  15. IMPACT Financial/reputational fallout: CyrusOne reportedly postponed/halted a bond sale after the data-center failure that disrupted CME, and confirmed to Bloomberg the ~11-hour outage was caused by human error.

Response by role

8 roles/6 recorded actions/37 playbook actions across 6 failure modes/no recorded action: First responder, Incident commander, Vendor / upstream provider

What each role did

Roles the sequence of events shows acting; every entry quotes its source line. Select a time to jump to it.

Role
Detect
Contain
Recover
Mechanical / cooling engineerCyrusOne onsite staff, contractors and engineering teams at CHI1 — not named
  • Prepare and drain the cooling towers for freezing weather without following standard winterization procedures
  • Engineering teams and contractors restart the chillers and rebuild chilled-water circulation
no record
Service recovery leadCyrusOne, which restored stable operations at CHI1
no record
no record
  • CyrusOne reports stable operation restored and additional cooling redundancy installed
Communications leadCME Group, which published the market-halt notice
no record
  • CME publishes a notice that markets are halted by a cooling issue and that it is working to resolve it
no record
CustomerCME Group, tenant running its trading systems at CHI1
no record
no record
Authority / investigatorCFTC and SEC, reportedly aware and monitoring
no record
no record

Role by role

Recorded actions / playbook actions per role. A role with 0 recorded actions does not appear in the sources.

No first responder is named; the record does not say who saw the first alarm — Meets the first alarm: on-shift technician or security in a facility, on-call engineer in a service.

On the record

No action by this role appears in the sources.

Playbook analyst guidance by failure mode, not a record of what happened

Detect
  • FM-01Walk the plant and read chilled-water flow and tower temperature after each freeze-prep step before the next startsASHRAE TC 9.9
  • FM-05Log chilled-water temperature and flow every few minutes during the restart to see whether circulation is steadyASHRAE TC 9.9
  • FM-02Check the signed method statement against what the contractor is doing at each towerChange management
  • FM-03Alarm on loss of chilled-water supply across more than one unit and send it to the on-call mechanical engineerASHRAE TC 9.9
  • FM-04Set high-temperature alarms on rack inlet and hall return air, and route them to the on-call lineASHRAE TC 9.9

No incident commander is named in the record — Owns every decision until formally relieved: site duty manager on scene, or the declared IC of a service incident.

On the record

No action by this role appears in the sources.

Playbook analyst guidance by failure mode, not a record of what happened

Prevent
  • FM-02Name one accountable supervisor for freeze-prep, covering both staff and contractors, before the work startsUptime OSCorrection of errors #4
Contain
  • FM-01Stop all further tower drain-down and re-establish chilled-water flow to the halls before any other actionNIMS / ICS
  • FM-05Set the order for returning IT load: bring it back only as chilled-water circulation is stableNIMS / ICS
  • FM-03Tell the tenant the plant has failed so it can start load-shed before inlet temperatures climbNIMS / ICS
  • FM-06Declare a market-wide halt rather than run partial service from an unstable siteISO 22301
  • FM-04Hold the load off the halls until cooling is proven stableNIMS / ICS

CyrusOne onsite staff, contractors and engineering teams at CHI1 — not named — Chillers, CRAH/CRAC, pumps, cooling towers and the thermal envelope of the white space.

On the record

  1. Prepare and drain the cooling towers for freezing weather without following standard winterization proceduresonsite staff and contractors began preparing/draining CHI1's cooling towers
  2. Engineering teams and contractors restart the chillers and rebuild chilled-water circulationCyrusOne mobilized engineering teams and contractors on-site to restart chillers

Playbook analyst guidance by failure mode, not a record of what happened

Prevent
  • FM-01Run freeze-prep as a checklist-gated changeover with two-person sign-off on each tower drain-downNFPA 70EImprovement #1
  • FM-01Dry-run the full freeze-prep sequence each season and audit tower drain-down and valve line-ups before the first hard freezeUptime OSImprovement #6
  • FM-05Pre-stage mobile cooling and restart procedures for the CHI1 plant, rehearsed in the pre-winter commissioningUptime OSImprovement #2
  • FM-03Provide N+1 or N+2 cooling with procedurally diverse changeover steps, so one lapse cannot trip every unitASHRAE TC 9.9Improvement #2
  • FM-03Install the additional redundancy to the CHI1 cooling systems that CyrusOne added after the eventUptime OSCorrection of errors #2
Contain
  • FM-01Restore the towers to their pre-changeover line-up and confirm each cooling unit is online before resumingASHRAE TC 9.9
  • FM-05Restart chillers at limited capacity and rebuild chilled-water circulation before adding more unitsASHRAE TC 9.9
  • FM-02Stop contractor work on any step that does not match the method statement and call the supervisorChange management
  • FM-03Bring standby chillers and pumps online in order, starting with the units that can restart with the towers as they areASHRAE TC 9.9

The contracting firm on the freeze-prep work — not named in any source — Third party whose product, service or network sits in the failure path.

On the record

No action by this role appears in the sources.

Playbook analyst guidance by failure mode, not a record of what happened

Prevent
  • FM-02Work to an approved method statement with on-site supervision and a two-person verify on live freeze-prepChange managementImprovement #3

CyrusOne, which restored stable operations at CHI1 — Restores customer service: failover, workload moves, capacity, backlog drain.

On the record

  1. CyrusOne reports stable operation restored and additional cooling redundancy installedrestored stable and secure operations at its Chicago 1 (CHI1) data center

Playbook analyst guidance by failure mode, not a record of what happened

Prevent
  • FM-04Wire BMS or DCIM high-temperature alarms to automated IT throttling before inlet limits are crossedASHRAE TC 9.9Correction of errors #6
Recover
  • FM-01Confirm tower and chiller status from the BMS and field before declaring freeze-prep completeUptime OS
  • FM-05Bring IT load back in stages and confirm temperatures at each stageASHRAE TC 9.9
  • FM-02Review the contractor boundary after the event and re-issue a verified method statementChange management
  • FM-03Restore chilled-water circulation to the halls and confirm supply temperature is stable before IT load returnsASHRAE TC 9.9Correction of errors #3
  • FM-04Review alarm thresholds against the temperatures actually reached and reset themUptime OS

CME Group, which published the market-halt notice — Status page, customer notices, regulators and press; one voice, timed updates.

On the record

  1. CME publishes a notice that markets are halted by a cooling issue and that it is working to resolve itCME issued a public notice that its markets were halted due to a cooling issue

Playbook analyst guidance by failure mode, not a record of what happened

Detect
  • FM-06Watch for a halt or loss of price feed and alert traders and clearing members at onceISO 22301
Contain
  • FM-06Publish the halt notice, with the reason and who is working to resolve itISO 22301
Recover
  • FM-05Tell the market when each product returns: EBS at about 07:00 ET, stock futures about 08:30 ETISO 22301

CME Group, tenant running its trading systems at CHI1 — The tenant or service user: their own redundancy, backups and continuity plan.

On the record

  1. CME halts or fails over its trading systems to stop generating heat and protect hardwareCME's trading systems (Globex and related markets) were halted/failed over

Playbook analyst guidance by failure mode, not a record of what happened

Prevent
  • FM-06Pursue geographically diverse cooling and power for critical matching enginesISO 22301Correction of errors #5
  • FM-06Test a full failover of the matching engines to a second siteNIST SP 800-34Improvement #5
  • FM-04Agree with the operator the inlet temperature at which the tenant sheds load, and test itASHRAE TC 9.9Lesson #5
Contain
  • FM-04Halt or fail over trading systems on the agreed temperature trigger, not after hardware limits are closeASHRAE TC 9.9
Recover
  • FM-03Return IT load to the halls in stages as supply temperature holdsASHRAE TC 9.9
  • FM-06Restart markets in sequence as each system is checked, with FX and futures firstNIST SP 800-34

CFTC and SEC, reportedly aware and monitoring — Regulator, investigator or court that establishes cause and obligations after the event.

On the record

  1. CFTC and SEC are reportedly aware and monitoring as futures trading resumesregulators (CFTC and SEC) reportedly aware and monitoring

Playbook analyst guidance by failure mode, not a record of what happened

Recover
  • FM-06Review market integrity after the halt before trading resumes in fullISO 22301Correction of errors #7

Failure mode & effects analysis (FMEA)

The cooling chain at CyrusOne's CHI1 data center in Aurora, Illinois, and the CME Group trading systems it serves: the cooling-tower freeze-preparation procedure and its contractor boundary, the chiller plant and its redundancy, thermal detection and protective load-shed, chiller restart and recovery, and the concentration of CME's matching engines on one campus. No official post-mortem exists. The record is press-sourced: CyrusOne statements relayed by DatacenterDynamics (confirmed), with Bloomberg, Reuters, CNBC and DC Pulse details cited but not re-fetched. Chiller counts, peak temperatures (the >100°F figure is unverified), detection timing and the skipped procedure step are undisclosed, and several sequence entries are forensic reconstructions. The only confirmed corrective action is that CyrusOne 'installed additional redundancy to the cooling systems', with no tonnage or design disclosed; every other action is unconfirmed or open.

6 failure modes/5 high priority/1 of 6 with a published action/total RPN 1799 → 1671 (−7%)

RPN = S × O × D, worst first. Thin bar: after the published action.
FM-01no published action432
FM-05no published action360
FM-02no published action324
FM-03320 → 192
FM-06no published action243
FM-04no published action120
Severity × occurrence. Lines bound the medium and high zones.
1122334455667788991010Occurrence →Severity →FM-06 Globally critical matching engines depend on the single Aurora campus, so one plant's thermal failure halts worldwide trading (S9 O3 D9)06FM-02 No method statement, supervision or independent verification gates the changeover at the contractor boundary (S9 O4 D9)02FM-01 Onsite staff and contractors do not follow standard procedures when draining the cooling towers ahead of a hard freeze (S9 O6 D8)01FM-03 One procedural lapse trips multiple cooling units together and no backup cooling path carries the load (S8 O5 D8); FM-05 Recovery is manual: chillers restart at limited capacity and IT returns in stages (S8 O5 D9)03, 05FM-04 No automated link from thermal alarms to IT load-shed is recorded; protection depends on the tenant halting its own systems (S5 O4 D6)04
Caught only after impactD ≥ 8
5 of 6
Actions that cut occurrenceO lowered
1
Actions that cut detectionD lowered
0
Actions that cut severityblast radius unchanged
0
FM-01 Onsite staff and contractors do not follow standard procedures when draining the cooling towers ahead of a hard freezeCooling-tower freeze-preparation (draining) procedure 9·6·8 432 —
Function
Transition the water-cooled tower plant for freezing weather without interrupting chilled-water supply
Effect
A chiller-plant failure takes multiple cooling units offline; CME halts its global futures and options markets for about 11 hours
Cause
Procedure execution failure during a seasonal changeover under live IT load (confirmed by CyrusOne as human error; the skipped step is not disclosed)
Prevention in place
A standard procedure existed but was not followed
Detection in place
None recorded before the plant tripped; when and how the failure was first detected is not disclosed
S 9
Took down a global derivatives exchange's futures and options trading, with no workaround for market participants, for about 11 hours: provider-wide outage of a foundational service, the rubric's 9. Not 10: no hazard to people is recorded and the facility was not lost.
O 6
Freeze preparation is routine seasonal work, and the only recorded guard was the procedure itself, which was not followed: 'occasional, weakly guarded'.
D 8
No verification caught the mis-sequenced changeover before units tripped; detection came after impact, though the exact detection path is not in the record.

Corrective action

  • Rebuild the freeze-prep SOP as a checklist-gated changeover with two-person sign-off and a seasonal dry-run (not publicly confirmed) Correction of errors #1

Who acts — playbook

Prevent
  • Mechanical / cooling engineer Run freeze-prep as a checklist-gated changeover with two-person sign-off on each tower drain-downNFPA 70EImprovement #1
  • Mechanical / cooling engineer Dry-run the full freeze-prep sequence each season and audit tower drain-down and valve line-ups before the first hard freezeUptime OSImprovement #6
Detect
  • First responder Walk the plant and read chilled-water flow and tower temperature after each freeze-prep step before the next startsASHRAE TC 9.9
Contain
  • Incident commander Stop all further tower drain-down and re-establish chilled-water flow to the halls before any other actionNIMS / ICS
  • Mechanical / cooling engineer Restore the towers to their pre-changeover line-up and confirm each cooling unit is online before resumingASHRAE TC 9.9
Recover
  • Service recovery lead Confirm tower and chiller status from the BMS and field before declaring freeze-prep completeUptime OS

On the record at this failure

  • Mechanical / cooling engineer Prepare and drain the cooling towers for freezing weather without following standard winterization procedures

Evidence

  • Reference #1 · press“staff and contractors failed to follow standard procedures when draining cooling towers ahead of freezing weather”
  • Sequence of events #12025-11-27 evening (CT) — On the live approach to a hard freeze in the Chicago suburbs (Thanksgiving-window reopen), onsite staff and contractors began preparing/draining CHI1's cooling towers for freezing weather but failed to follow standard procedures for the winterization changeover (CyrusOne, confirmed to Bloomberg).
  • Contributing factor #1PROCEDURAL EXECUTION FAILURE DURING FREEZE-PREP (root, CONFIRMED): CyrusOne confirmed to Bloomberg that onsite staff and contractors failed to follow standard procedures when draining/preparing the cooling towers ahead of freezing weather (via DatacenterDynamics) - a seasonal cold-weather changeover mishandled on the live approach to a hard freeze.
  • Metric #1Total outage duration: ~11 hours (reported 'over 11 hours')
  • Improvement #3“no verification caught the mis-sequenced changeover before multiple units tripped”
FM-05 Recovery is manual: chillers restart at limited capacity and IT returns in stagesChiller restart and cooling reconstitution 8·5·9 360 —
Function
Restore chilled-water circulation quickly after a plant trip
Effect
Markets resume in stages, EBS at about 07:00 ET and full reopen at about 08:30 ET on 28 November per CNBC (not reconfirmed), about 11 hours after the halt
Cause
No recorded pre-staged rapid-response cooling; restart depended on mobilising engineers and contractors on site
Prevention in place
None recorded
Detection in place
Not applicable before the incident; recovery time was learned during it
S 8
This mode sets the length of the outage rather than its existence: hours of full outage of a major service is the rubric's 8.
O 5
A manual restart path applies to any plant-wide trip; present as a condition though rarely exercised.
D 9
No rehearsal or pre-staged capacity is recorded that would have shown recovery time in advance. The 'temporary and supplemental chillers' detail is unverified and not relied on.

Corrective action

  • Common-mode-resistant redundancy plus pre-staged rapid-response mobile cooling Improvement #2

Who acts — playbook

Prevent
  • Mechanical / cooling engineer Pre-stage mobile cooling and restart procedures for the CHI1 plant, rehearsed in the pre-winter commissioningUptime OSImprovement #2
Detect
  • First responder Log chilled-water temperature and flow every few minutes during the restart to see whether circulation is steadyASHRAE TC 9.9
Contain
  • Mechanical / cooling engineer Restart chillers at limited capacity and rebuild chilled-water circulation before adding more unitsASHRAE TC 9.9
  • Incident commander Set the order for returning IT load: bring it back only as chilled-water circulation is stableNIMS / ICS
Recover
  • Service recovery lead Bring IT load back in stages and confirm temperatures at each stageASHRAE TC 9.9
  • Communications lead Tell the market when each product returns: EBS at about 07:00 ET, stock futures about 08:30 ETISO 22301

On the record at this failure

  • Mechanical / cooling engineer Engineering teams and contractors restart the chillers and rebuild chilled-water circulation

Evidence

  • Technical deep-dive“Recovery was mechanical and manual”
  • Sequence of events #102025-11-28 early hours — Chillers restarted at limited capacity and cooling reconstituted to rebuild chilled-water circulation to a stable state (any 'temporary/supplemental chillers and pipework' detail is attributed to DC Pulse and is unverified).
  • Metric #6EBS markets resume time: ~07:00 ET, 2025-11-28 (not independently reconfirmed)
  • Metric #7Full market reopen time: ~08:30 ET, 2025-11-28 (not independently reconfirmed)
  • Sequence of events #82025-11-27/28 overnight — Emergency MECHANICAL response (no fire department / 911): CyrusOne mobilized engineering teams and contractors on-site to restart chillers and reconstitute chilled-water circulation.
FM-02 No method statement, supervision or independent verification gates the changeover at the contractor boundaryContractor-boundary change management for live freeze-prep 9·4·9 324 —
Function
Verify each freeze-prep step done by staff and contractors before it affects the live plant
Effect
The lapse is not caught before the chiller plant trips
Cause
Change-management gap spanning onsite personnel and contractors; no source names the procedure document, firm or skipped step
Prevention in place
None recorded
Detection in place
None recorded
S 9
Another route to the same exchange-wide outage, so it carries FM-01's severity.
O 4
Scored below FM-01 so the one event is not counted twice at full weight; the dossier itself infers this gap ('implying') rather than stating it.
D 9
No verification step is recorded; the gap became visible only through the plant failure.

Corrective action

  • Method statements, supervision and two-person verification at the contractor boundary (not publicly confirmed) Correction of errors #4

Who acts — playbook

Prevent
  • Vendor / upstream provider Work to an approved method statement with on-site supervision and a two-person verify on live freeze-prepChange managementImprovement #3
  • Incident commander Name one accountable supervisor for freeze-prep, covering both staff and contractors, before the work startsUptime OSCorrection of errors #4
Detect
  • First responder Check the signed method statement against what the contractor is doing at each towerChange management
Contain
  • Mechanical / cooling engineer Stop contractor work on any step that does not match the method statement and call the supervisorChange management
Recover
  • Service recovery lead Review the contractor boundary after the event and re-issue a verified method statementChange management

Evidence

  • Contributing factor #5“no accessible source names the specific procedure document”
  • Improvement #3Process: Institute change-management controls at the contractor boundary for any live freeze-prep switchover - approved method statements, on-site supervision, and a two-person verify step - since the lapse spanned both onsite personnel and contractors and no verification caught the mis-sequenced changeover before multiple units tripped.
  • Root cause“onsite staff and contractors failed to follow standard procedures”
FM-03 One procedural lapse trips multiple cooling units together and no backup cooling path carries the loadCHI1 chiller plant and backup cooling 8·5·8 320 192
Function
Keep chilled water flowing to the data halls if one unit or one changeover step fails
Effect
Chilled-water circulation to the halls is lost and room and rack-inlet temperatures rise until CME halts its trading systems
Cause
Common-mode exposure: the redundant units shared the same changeover, so redundancy did not cover this failure mode
Prevention in place
Installed cooling redundancy, which did not carry the load
Detection in place
Not disclosed
S 8
Loss of cooling to the halls is the physical cause of the halt; scored 8 rather than 9 so the exchange outage already carried by FM-01 is not counted again at full weight.
O 5
Any changeover touching shared plant exercises the common mode; between 'infrequent' and 'occasional'.
D 8
Nothing recorded warned that redundancy would not survive a changeover error; it was learned when the units tripped.

Corrective action

  • Install additional redundancy to the CHI1 cooling systems Correction of errors #2

After action: S8 · O3 · D8 → RPN 192. CyrusOne confirmed it installed additional cooling redundancy, so one tripped unit is less likely to leave the halls without cooling (O 5→3). The reduction is kept small because no tonnage or design is disclosed, and the dossier cannot say whether the new redundancy is free of the same freeze-prep common mode.

Who acts — playbook

Prevent
  • Mechanical / cooling engineer Provide N+1 or N+2 cooling with procedurally diverse changeover steps, so one lapse cannot trip every unitASHRAE TC 9.9Improvement #2
  • Mechanical / cooling engineer Install the additional redundancy to the CHI1 cooling systems that CyrusOne added after the eventUptime OSCorrection of errors #2
Detect
  • First responder Alarm on loss of chilled-water supply across more than one unit and send it to the on-call mechanical engineerASHRAE TC 9.9
Contain
  • Incident commander Tell the tenant the plant has failed so it can start load-shed before inlet temperatures climbNIMS / ICS
  • Mechanical / cooling engineer Bring standby chillers and pumps online in order, starting with the units that can restart with the towers as they areASHRAE TC 9.9
Recover
  • Service recovery lead Restore chilled-water circulation to the halls and confirm supply temperature is stable before IT load returnsASHRAE TC 9.9Correction of errors #3
  • Customer Return IT load to the halls in stages as supply temperature holdsASHRAE TC 9.9

Evidence

  • Sequence of events #2“experienced a chiller plant failure affecting multiple cooling units”
  • Metric #2Cooling units affected: 'multiple cooling units' (common-mode; exact count not disclosed)
  • Contributing factor #2INADEQUATE / COMMON-MODE MECHANICAL REDUNDANCY: a single procedural lapse took 'multiple cooling units' offline at once with no backup cooling carrying the load, evidenced by CyrusOne's post-incident fix of having 'installed additional redundancy to the cooling systems' (confirmed verbatim via DCD) - i.e. the fault-tolerant protection a resilient plant should have provided was effectively absent for this failure mode.
  • Root cause“is an admission that pre-incident backup cooling did not save the load”
FM-06 Globally critical matching engines depend on the single Aurora campus, so one plant's thermal failure halts worldwide tradingPlacement of CME matching engines on one campus 9·3·9 243 —
Function
Keep global price discovery running if one site loses cooling
Effect
Traders lose access to futures prices for commodities and stocks across CME's derivatives markets for about 11 hours
Cause
Single-site concentration with no geographically diverse fallback recorded
Prevention in place
None recorded
Detection in place
Customer-visible impact
S 9
Concentration is what made a facility cooling fault an exchange-wide outage with no workaround.
O 3
Needs a site-level failure first, which is infrequent. The concentration commentary is attributed to DC Pulse and could not be re-fetched.
D 9
Seen through market participants losing access.

Corrective action

  • Geographically diverse cooling and power architecture for critical matching engines and a review of single-site concentration (open, not publicly confirmed) Correction of errors #5

Who acts — playbook

Prevent
  • Customer Pursue geographically diverse cooling and power for critical matching enginesISO 22301Correction of errors #5
  • Customer Test a full failover of the matching engines to a second siteNIST SP 800-34Improvement #5
Detect
  • Communications lead Watch for a halt or loss of price feed and alert traders and clearing members at onceISO 22301
Contain
  • Incident commander Declare a market-wide halt rather than run partial service from an unstable siteISO 22301
  • Communications lead Publish the halt notice, with the reason and who is working to resolve itISO 22301
Recover
  • Authority / investigator Review market integrity after the halt before trading resumes in fullISO 22301Correction of errors #7
  • Customer Restart markets in sequence as each system is checked, with FX and futures firstNIST SP 800-34

Evidence

  • Contributing factor #4SINGLE-SITE CONCENTRATION OF CRITICAL WORKLOAD: CME's matching engines ran from the single Aurora campus, so one plant's thermal failure halted global futures/options price discovery - a concentration-risk / missing geographic-diversity theme raised in trade commentary (attributed to DC Pulse; that specific commentary could not be independently re-fetched).
  • Sequence of events #62025-11-27/28 overnight — Global markets knocked out: the halt prevented traders from accessing futures prices for commodities and stocks across CME Group's derivatives markets (specific benchmark list per trade reporting: S&P 500, Nasdaq, Treasuries, WTI, gold, Nikkei, palm oil - not independently reconfirmed).
  • Metric #1Total outage duration: ~11 hours (reported 'over 11 hours')
FM-04 No automated link from thermal alarms to IT load-shed is recorded; protection depends on the tenant halting its own systemsThermal detection and protective load-shed 5·4·6 120 —
Function
Alarm on rising hall temperatures and shed IT heat load before safe inlet limits are crossed
Effect
CME halts its trading systems to protect hardware; hall temperatures above 100°F are reported by a secondary summary but not confirmed
Cause
Detection not wired to protection (an analyst recommendation in the dossier; the actual alarm path and timing are not disclosed)
Prevention in place
Tenant-initiated protective shutdown
Detection in place
BMS/DCIM alarms are inferred, not confirmed; no source states when the high-temperature threshold tripped
S 5
The halt itself is scored in FM-01; this mode covers the added exposure of hardware to heat before load was shed, which the record shows only as customer-visible degradation with no reported hardware damage.
O 4
It matters only after a plant-wide cooling loss, which needs an unusual combination: 'infrequent'.
D 6
Rising temperature was evidently seen, since CME halted, but nothing automated acted on it: 'detected at onset, not prevented'. Scored with low confidence because detection timing is undisclosed.

Corrective action

  • Wire thermal early-warning to automated IT load-shed thresholds (open, not publicly confirmed) Correction of errors #6

Who acts — playbook

Prevent
  • Service recovery lead Wire BMS or DCIM high-temperature alarms to automated IT throttling before inlet limits are crossedASHRAE TC 9.9Correction of errors #6
  • Customer Agree with the operator the inlet temperature at which the tenant sheds load, and test itASHRAE TC 9.9Lesson #5
Detect
  • First responder Set high-temperature alarms on rack inlet and hall return air, and route them to the on-call lineASHRAE TC 9.9
Contain
  • Customer Halt or fail over trading systems on the agreed temperature trigger, not after hardware limits are closeASHRAE TC 9.9
  • Incident commander Hold the load off the halls until cooling is proven stableNIMS / ICS
Recover
  • Service recovery lead Review alarm thresholds against the temperatures actually reached and reset themUptime OS

On the record at this failure

Evidence

  • Sequence of events #4“No accessible source states the exact minute the high-temp threshold tripped.”
  • Sequence of events #52025-11-27 late evening (ET) — Protective compute shutdown: to stop generating heat and protect hardware, CME's trading systems (Globex and related markets) were halted/failed over - an 'evacuation of compute' rather than any occupant evacuation (unmanned mechanical failure, no life-safety event).
  • Metric #5Peak data-hall temperature (reported): >100degF (UNVERIFIED - not disclosed by CyrusOne; from a secondary incident summary)
  • Improvement #4Safety: Tighten thermal early-warning and automated load-shed thresholds (BMS/DCIM high-temp alarms tied to protective IT throttling) so a chiller-plant trip is caught and heat load shed before halls exceed safe inlet temperatures - closing detection-to-protection latency.
Scoring rubric and method

Scales adapted from IEC 60812:2018 and AIAG-VDA. RPN = S × O × D. High: S ≥ 9 with O ≥ 4 or D ≥ 7, or RPN ≥ 300. Medium: RPN ≥ 120 or S ≥ 7. Severity overrides the product: 9 × 2 × 9 = 162 would otherwise hide a region-wide outage nothing could catch. Quotes are checked verbatim against this dossier; a revised score needs a published action. RZ analyst assessment, not an operator document.

Severity

10Hazard to people, or loss of the facility / several regions
9Region-wide or provider-wide outage of a foundational service, no workaround
8Full outage of a major service for hours
7Major degradation of a major service
6Partial outage confined to one zone or one service
5Customer-visible degradation
4Limited customer impact
3Internal impact only
2Negligible
1No effect

Occurrence

10Near certain: the cause is present in normal operation
8Frequent: routine work exercises the cause
6Occasional: a foreseeable slip or condition, weakly guarded
4Infrequent: needs an unusual combination
2Remote: guarded by design
1Eliminated by design

Detection

10No control could detect it
9Detected only through customer impact
8Detected after impact by internal monitoring
6Detected at onset, not prevented
4Detected before impact with time to act
2Automated interlock almost certainly stops it
1Certain to be stopped

Root cause and contributing factors

PRIMARY EQUIPMENT / FAILURE MECHANISM. This was a loss-of-cooling (thermal) event, not a fire — no ignition source, no combustion. The failed system was the primary water-cooled CHILLER PLANT serving CyrusOne's CHI1 (Chicago 1 / "CH1") data center in Aurora, Illinois. In CyrusOne's own words the CHI1 facility "experienced a chiller plant failure affecting multiple cooling units" (CyrusOne statement, relayed by DatacenterDynamics).
Full root-cause narrative
Multiple cooling units dropped offline together, chilled-water circulation to the data halls was lost, and rack-inlet/room temperatures rose until CME Group's trading engines had to be halted to protect hardware. STATED ROOT CAUSE — HUMAN / PROCEDURAL (CONFIRMED). CyrusOne confirmed to Bloomberg that the ~11-hour outage was caused by human error: onsite staff and contractors failed to follow standard procedures when DRAINING/PREPARING the cooling towers ahead of freezing weather (CyrusOne to Bloomberg, via DatacenterDynamics). It occurred on the Thanksgiving-window reopen (evening of Nov 27, 2025, into Nov 28) as a hard freeze approached the Chicago suburbs. The confirmed mechanism is specifically the cooling-tower freeze-preparation/draining step being mishandled — which cascaded into a chiller-plant trip taking multiple cooling units offline. The fault sits in operating-procedure execution during a seasonal cold-weather changeover, not equipment age or a design defect. NOTE: the widely-repeated exact phrasing "preparing the cooling towers for freezing temperatures" is a paraphrase; the confirmed source wording describes staff/contractors failing to follow standard procedures when DRAINING cooling towers ahead of freezing weather. LATENT / SYSTEMIC ROOT. First, MECHANICAL REDUNDANCY DID NOT CARRY THE LOAD: a single procedural lapse during freeze-prep took "multiple cooling units" down at once with no effective backup cooling path — a common-mode failure that a fault-tolerant plant with procedurally diverse changeover steps should have survived. CyrusOne's own remedy — it "installed additional redundancy to the cooling systems" (CyrusOne, confirmed verbatim via DCD) — is an admission that pre-incident backup cooling did not save the load. Second, CONCENTRATION RISK: CME ran globally-critical matching engines out of the single Aurora campus, so one plant's thermal failure halted worldwide futures/options price discovery. No chiller make/model, refrigerant, unit age, or the exact hydraulic detail (frozen tower basin, condenser-water freeze, free-cooling/glycol changeover valve, or low-ambient lockout) has been publicly disclosed — the confirmed record stops at the mishandled cooling-tower freeze-preparation.

Contributing factors by category

Contributing factors by category — CyrusOnePeople: Freeze-prep steps not followed. Process: No contractor-boundary checks; Live-load winterization. Design: Common-mode cooling units; Alarms not wired to load-shed; Engines on one campus. Equipment: Chiller plant trips together. Environment: Hard freeze approaching. Effect: CME markets halted ~11 h.CME markets halted ~11 hDesignCommon-mode cooling unitsAlarms not wired to load-shedEngines on one campusPeopleFreeze-prep steps not followedEnvironmentHard freeze approachingProcessNo contractor-boundary checksLive-load winterizationEquipmentChiller plant trips together
Each short label stands for a contributing factor or failure mode recorded in this dossier; the full sentences are listed below.
  • PROCEDURAL EXECUTION FAILURE DURING FREEZE-PREP (root, CONFIRMED): CyrusOne confirmed to Bloomberg that onsite staff and contractors failed to follow standard procedures when draining/preparing the cooling towers ahead of freezing weather (via DatacenterDynamics) - a seasonal cold-weather changeover mishandled on the live approach to a hard freeze.
  • INADEQUATE / COMMON-MODE MECHANICAL REDUNDANCY: a single procedural lapse took 'multiple cooling units' offline at once with no backup cooling carrying the load, evidenced by CyrusOne's post-incident fix of having 'installed additional redundancy to the cooling systems' (confirmed verbatim via DCD) - i.e. the fault-tolerant protection a resilient plant should have provided was effectively absent for this failure mode.
  • COLD-WEATHER / SEASONAL-TRANSITION TIMING RISK: the failure hit during a hard-freeze approach in the Chicago suburbs on the Thanksgiving-window reopen (evening of Nov 27, into Nov 28), a known high-risk winterization window for water-cooled tower plants, executed under live IT load (CyrusOne statement; DCD).
  • SINGLE-SITE CONCENTRATION OF CRITICAL WORKLOAD: CME's matching engines ran from the single Aurora campus, so one plant's thermal failure halted global futures/options price discovery - a concentration-risk / missing geographic-diversity theme raised in trade commentary (attributed to DC Pulse; that specific commentary could not be independently re-fetched).
  • CONTRACTOR-BOUNDARY / CHANGE-MANAGEMENT GAP: the lapse spanned both onsite personnel and contractors, implying a method-statement / supervision boundary where the freeze-prep steps were not verified - though no accessible source names the specific procedure document, the contracting firm, or which checklist step was skipped (disclosed uncertainty; CyrusOne via Bloomberg/DCD).

Analysis

What happened

On the evening of Nov 27, 2025 (into Nov 28), CyrusOne's CHI1 (Chicago 1 / 'CH1') data center in Aurora, Illinois 'experienced a chiller plant failure affecting multiple cooling units' (CyrusOne, confirmed via DatacenterDynamics). Chilled-water cooling to the halls was lost as a hard freeze approached the Chicago suburbs, and CME Group - a tenant whose trading engines run from the campus - halted its markets to protect hardware. Trading resumed after roughly 11 hours. This was a loss-of-cooling (thermal) event, not a fire: there was no ignition, combustion, or suppression discharge.

Why it happened (root and latent causes)

CyrusOne confirmed to Bloomberg the outage was caused by human error - onsite staff and contractors failed to follow standard procedures when draining/preparing the cooling towers ahead of freezing weather. Beneath that sit two latent gaps: (1) common-mode redundancy failure, since one mis-sequenced changeover took 'multiple cooling units' down together with no effective backup path - later confirmed by CyrusOne 'installing additional redundancy to the cooling systems'; and (2) single-site concentration of globally-critical workload. No chiller make/model, refrigerant, unit age, or exact hydraulic detail was disclosed.

Why it mattered (impact and concentration risk)

Because CME's matching engines run from the single Aurora campus, a plant-level thermal failure became worldwide market downtime - traders lost access to futures prices for commodities and stocks across CME Group's derivatives markets for ~11 hours. Trade reporting listed benchmarks including S&P 500, Nasdaq, Treasuries, WTI, gold, Nikkei and palm oil (not independently reconfirmed here). The event also carried financial/reputational fallout: CyrusOne reportedly postponed a bond sale afterward (Bloomberg; not independently reconfirmed).

Response and recovery

There was no suppression system to activate - the cooling plant itself was the failed 'suppression analogue.' Recovery was mechanical and manual: chillers were restarted at limited capacity and chilled-water circulation reconstituted until IT - and CME's markets - could be brought back in stages (EBS ~07:00 ET, full reopen ~08:30 ET per CNBC, not reconfirmed). CyrusOne then reported it 'restored stable and secure operations at its Chicago 1 (CHI1) data center' and 'installed additional redundancy to the cooling systems' (both confirmed verbatim).

Verification status and source limitations

This review directly re-confirmed, via a reader-proxy to DatacenterDynamics relaying CyrusOne's statements: the CHI1/Aurora location, the 'chiller plant failure affecting multiple cooling units' phrasing, the human-error root cause tied to cooling-tower freeze-prep, the ~11-hour duration, the 109MW / 450,000 sq ft / 3-DC campus profile, and the two CyrusOne quotes on restored operations and added redundancy. It could NOT re-fetch Bloomberg, Reuters, CNBC or DC Pulse (bot-block/CAPTCHA) - so precise resume times, the CFTC/SEC line, the benchmark product list, the bond-sale detail, the $130M/15-year sale-leaseback, the >100degF temperature, and the 'temporary and supplemental chillers and pipework' phrase remain cited-but-not-independently-reconfirmed and, where noted, unverified.

Technical deep-dive
MECHANISM OF A COLD-WEATHER CHILLER-PLANT FAILURE. Paradoxically, this data-center thermal event was triggered by COLD, not heat. Water-cooled chiller plants reject heat through cooling towers that evaporate water to open air. When ambient temperatures approach and cross freezing, exposed condenser-water in tower basins, fill, and outdoor pipework can freeze, and the plant must be transitioned for cold weather — basins drained or heated, valves switched to free-cooling/glycol loops, flows and setpoints reconfigured — following a defined freeze-prep procedure. CyrusOne's confirmed account is that this changeover was executed incorrectly by onsite personnel and contractors who failed to follow standard procedures when preparing/draining the cooling towers ahead of freezing weather, and that this procedural lapse produced a chiller-plant failure affecting multiple cooling units (CyrusOne to Bloomberg, via DCD). The word "multiple" is the critical forensic signal: this was a COMMON-MODE trip, in which one mis-sequenced changeover simultaneously compromised more than one unit rather than a single random component failure that redundancy could absorb. THERMAL CASCADE INTO IT. Data halls have low thermal mass relative to their heat load; against the campus's 109MW IT capacity, tens of megawatts of server heat with no chilled water raises room and rack-inlet temperatures within minutes. A widely-cited incident summary reports hall temperatures exceeding 100°F, but CyrusOne did NOT disclose a per-sensor peak — treat >100°F as an unverified reported figure, not a confirmed measurement. As inlet air crossed safe thresholds, the correct protective response is exactly what happened: shed the heat source. CME halted its trading systems — effectively an "evacuation of compute" — to stop generating heat and protect hardware while cooling was reconstituted, rather than risk mass server thermal damage. RECONSTITUTION OF COOLING. There was no suppression system to activate because there was no fire; the "suppression analogue" — the cooling plant — was the very thing that failed. Recovery was mechanical and manual: chillers were restarted at limited capacity and cooling reconstituted until chilled-water circulation was stable enough to bring IT load — and CME's markets — back online in stages, with all trading resumed after roughly 11 hours. CyrusOne subsequently "installed additional redundancy to the cooling systems" and reported it "restored stable and secure operations" at CHI1 (both confirmed verbatim via DCD). NOTE ON UNCERTAINTY: no accessible primary source gives the exact minute the high-temperature threshold tripped, the peak hall temperature by sensor, the number of chillers affected versus total installed, or any mobile-chiller tonnage; the phrase "temporary and supplemental chillers and pipework" is attributed to a secondary trade blog (DC Pulse) that could not be re-fetched and does NOT appear in CyrusOne's DCD-relayed statement, so it is treated as unverified.

Corrective actions and lessons

Correction of errors

ActionOwnerStatus
Rebuild cooling-tower freeze-prep/winterization SOP as a checklist-gated changeover with independent two-person sign-off and seasonal dry-runCyrusOne Critical Facilities OperationsNot publicly confirmed (implied by stated root cause; only the redundancy fix was disclosed)
Install additional redundancy to the CHI1 cooling systemsCyrusOneDone (CyrusOne confirmed it 'installed additional redundancy to the cooling systems')
Restore stable and secure operations at CHI1 AuroraCyrusOneDone (CyrusOne confirmed restored stable and secure operations)
Impose change-management controls (method statements, supervision, two-person verify) at the contractor boundary for live freeze-prepCyrusOne / contracting firmNot publicly confirmed
Pursue geographically diverse cooling/power architecture for critical matching engines and review single-site concentrationCME GroupOpen / not publicly confirmed
Wire thermal early-warning to automated IT load-shed thresholds (BMS/DCIM)CyrusOne / CMEOpen / not publicly confirmed
Regulatory awareness and market-integrity review of the outageCFTC / SECReported aware/monitoring per Reuters (not independently reconfirmed)

Lessons learnt

  • A cooling plant is a single point of failure equal to any power system: a mishandled seasonal winterization step - not equipment age or a fire - halted a global exchange for ~11 hours, so freeze-prep is a critical, life-of-the-facility procedure, not routine maintenance.
  • Redundancy that shares a common human/procedural mode is not redundancy: one mis-sequenced changeover took 'multiple cooling units' offline together, and the operator's after-the-fact addition of redundancy is proof the pre-incident backup path did not carry the load.
  • Concentration risk is systemic risk: running globally-critical matching engines from one campus means one plant's thermal failure becomes worldwide market downtime - geographic diversity is a resilience requirement, not a luxury.
  • Contractor-boundary work needs the tightest change control: because the lapse spanned staff and contractors, method statements, supervision, and independent verification must gate any live-load seasonal switchover.
  • Detection must be wired to protection: rising hall temperatures should auto-trigger load-shed/throttling before safe inlet limits are crossed, rather than relying on a downstream tenant (CME) to halt compute to save the hardware.
  • Public disclosure was partial: the operator confirmed human error and 'multiple cooling units' but never released chiller counts, refrigerant, peak sensor temperatures, or mobile-cooling tonnage - post-incidents should not be reconstructed as if those undisclosed specifics are established fact.

Improvements

  • MaintenanceRebuild the cooling-tower freeze-prep / winterization procedure as a verified, checklist-gated seasonal changeover with independent two-person sign-off - CyrusOne's own confirmed root cause is that staff and contractors failed to follow standard procedures when draining/preparing the cooling towers ahead of freezing weather, so procedure EXECUTION and verification, not just the document, must be hardened.
  • DesignProvide genuine common-mode-resistant mechanical redundancy (N+1/N+2 with procedurally diverse changeover steps) plus pre-staged rapid-response mobile cooling - implementing the very fix CyrusOne applied after the fact (it 'installed additional redundancy to the cooling systems').
  • ProcessInstitute change-management controls at the contractor boundary for any live freeze-prep switchover - approved method statements, on-site supervision, and a two-person verify step - since the lapse spanned both onsite personnel and contractors and no verification caught the mis-sequenced changeover before multiple units tripped.
  • SafetyTighten thermal early-warning and automated load-shed thresholds (BMS/DCIM high-temp alarms tied to protective IT throttling) so a chiller-plant trip is caught and heat load shed before halls exceed safe inlet temperatures - closing detection-to-protection latency.
  • Design/Resilience: For globally-critical workloads such as exchange matching engines, pursue redundant, geographically diverse cooling and power architectures so a single site's thermal failure cannot halt worldwide price discovery.
  • Maintenance/Assurance: Run a pre-winter commissioning and dry-run of the full freeze-prep sequence each season, with an independent audit of tower drain-down, basin-heater energization, and free-cooling/glycol valve line-ups before the first hard freeze.

References and provenance

Quotes are short, attributed, and for provenance only; the analysis is original. Last verified 2026-08-02 (seed — pending deep research).

Root access required

The DC Incidents dossier is a root-only module. Sign in with an authorized account to continue.

Back to Home