AWS Sydney 2016: Voltage Sag Drains the Rotary UPS, One Zone Loses Power
Summary
On 4 June 2016 (5 June in Sydney) storms took out a substation and the grid sagged rather than failed. In one AWS facility the breakers isolating the rotary UPS opened too slowly, the flywheel energy drained into the grid and both power line-ups dropped. Power was back in 81 minutes; a recovery bug and storage drive failures stretched customer recovery to about 9.5 hours.
- Users affected
- A significant number of EC2 instances and EBS volumes in one Sydney Availability Zone; launch errors across the Region until failover.
- Duration
- 9h 35m — Trigger 22:25 PDT 4 Jun → nearly all instances recovered 08:00 PDT 5 Jun (9 h 35 min)
- Financial
- Not disclosed
- Scope
- Single Availability Zone
- Site
- AWS facility in the Sydney Region (not named) · Sydney, Australia, ap-southeast-2
- Services down
- Amazon EC2, Amazon EBS, EC2 launch APIs, Elastic Load Balancing registration
How the defences failed
One Availability Zone in a major region; multi-zone customers stayed up. Duration (5): about 9 h 35 min from trigger to nearly all instances back, inside the 4–12 h band. Cost not disclosed.
All 8 impact metrics
| Utility loss | 22:25 PDT 4 Jun (15:25 AEST 5 Jun) |
| Facility power out | 1 hour 21 minutes (22:25 → 23:46 PDT) |
| Launch APIs failed away from the zone | 23:42 PDT, 1 hour 17 minutes after the trigger |
| Instances and volumes back by 01:00 PDT | over 80% |
| DNS errors recovered | 02:49 PDT |
| Nearly all instances recovered | 08:00 PDT, 9 hours 35 minutes after the trigger |
| EBS volumes not automatically recoverable | under 0.01% of the zone's volumes |
| EBS design annual failure rate quoted | 0.1%–0.2% |
Sequence of events
- TRIGGER Severe weather causes the utility provider to lose a regional substation; utility power is lost to multiple AWS facilities in the Sydney Region.Utility / grid operator
- TRIGGER The grid failure arrives as an unusually long voltage sag rather than a clean outage.
- CASCADE In one facility the breakers that isolate the diesel rotary UPS (DRUPS) from the utility fail to open quickly enough, and the DRUPS flywheel energy drains into the degraded grid.
- CASCADE Several DRUPS line-ups shut down, so generators that had started cannot be connected to the racks; affected instances lose both their primary and secondary power.
- IMPACT A significant number of EC2 instances and their EBS volumes in one Availability Zone lose power.
- IMPACT Customers get errors when launching new instances or scaling auto-scaling groups in the Region.
- DETECTION On-site technicians inspect the power line-ups to establish when it is safe to re-engage them by hand; AWS calls a DRUPS shutting down this fast unusual.Authorised electrical person
- MITIGATION The team completes a manual failover away from degraded services in the affected zone; customers can launch instances in the unaffected Availability Zones.Operations lead
- RECOVERY On-site technicians manually re-engage the power line-ups and power is restored.Authorised electrical person
- RECOVERY Automated systems begin bringing customer EC2 instances and EBS volumes back online.
- CASCADE Some instances see DNS resolution failures while the zone's internal DNS hosts come back and carry the recovery load.
- CASCADE The APIs recover but are slow to propagate state changes: new resources are not visible, some instances appear stuck in pending or shutting down, and adding instances to load balancers is slow.
- RECOVERY Over 80% of the impacted customer instances and volumes are back online.
- RECOVERY DNS error rates recover.
- CASCADE A latent bug in the instance management software stops automatic recovery of the remaining instances; the team recovers the remaining instances by hand over several hours.Service recovery lead
- IMPACT A small number of storage servers suffered failed hard drives; EBS volumes whose replicas sat on two failed servers cannot be restored automatically (under 0.01% of the zone's volumes).
- RECOVERY The EBS team manually recovers as many damaged storage servers as possible, a slow process that keeps some volumes out much longer.Service recovery lead
- RESTORED Nearly all instances are recovered.
Response by role
What each role did
Roles the sequence of events shows acting; every entry quotes its source line. Select a time to jump to it.
Role by role
Recorded actions / playbook actions per role. A role with 0 recorded actions does not appear in the sources.
The utility provider, not named — External owner of the supply: switching at the substation, load shedding, restoration.
On the record
Playbook analyst guidance by failure mode, not a record of what happened
AWS on-site technicians — Switching, isolation and lock-out of power sources, and safe re-energisation.
On the record
- Inspected the line-ups to decide when re-engaging was safe
On-site technicians inspect the power line-ups
- Re-engaged the line-ups by hand and restored power
manually re-engage the power line-ups
Playbook analyst guidance by failure mode, not a record of what happened
AWS operations team — Technical lead who diagnoses and drives the fix; the subject-matter expert at the keyboard or the switchboard.
On the record
Playbook analyst guidance by failure mode, not a record of what happened
- FM-05Design regional APIs so they shed a failed zone automaticallySRE incident mgmtCorrection of errors #4
- FM-02Alert when both feeds to a rack group drop within the same secondUptime OSContributing factor #3
- FM-03Track the share of instances recovered automatically and alert when it stallsSRE incident mgmtLesson #4
- FM-05Alert on launch error rate per zone, not only per regionSRE incident mgmtContributing factor #6
- FM-01Fail control-plane services away from the zone as soon as a line-up dropsSRE incident mgmtCorrection of errors #5
- FM-04Restore from snapshots where a server cannot be repairedISO 22301Lesson #6
AWS EC2 and EBS recovery teams — Restores customer service: failover, workload moves, capacity, backlog drain.
On the record
- Recovered instances the automation could not
the team recovers the remaining instances by hand
- Repaired damaged storage servers by hand
The EBS team manually recovers
Playbook analyst guidance by failure mode, not a record of what happened
- FM-03Run recovery workflows on spare long-running hosts on a scheduleSRE incident mgmtCorrection of errors #3
- FM-04List volumes whose replicas are all on failed servers as soon as power returnsNIST SP 800-34Contributing factor #5
- FM-02Move customer launches to unaffected zones while power is outSRE incident mgmtCorrection of errors #5
- FM-03Switch to manual recovery for instances the automation cannot restoreITIL 4Correction of errors #6
- FM-05Fail launches away from the degraded zone at onceSRE incident mgmtCorrection of errors #5
- FM-04Prioritise manual repair of the storage servers that hold the only copiesNIST SP 800-34Correction of errors #6
- FM-01Restart instances in order once both line-ups are proven stableSRE incident mgmtCorrection of errors #6
The AWS Team, Post-Event Summary — Status page, customer notices, regulators and press; one voice, timed updates.
On the record
No action by this role appears in the sources.
Playbook analyst guidance by failure mode, not a record of what happened
- FM-04Tell owners of affected volumes early and point them to their snapshotsITIL 4Contributing factor #5
Failure mode & effects analysis (FMEA)
The facility's dual DRUPS power line-ups and their utility isolation, plus the EC2/EBS recovery path and launch APIs, from AWS's own summary.
- Caught only after impactD ≥ 8
- 1 of 5
- Actions that cut occurrenceO lowered
- 3
- Actions that cut detectionD lowered
- 2
- Actions that cut severityblast radius unchanged
- 0
FM-01 During a long voltage sag the breakers do not open fast enough and the flywheel energy drains into the gridDRUPS input isolation breakers 9·3·8 216 108
- Function
- Island the rotary UPS from a bad grid so its flywheel feeds only the load until the diesel engages
- Effect
- DRUPS trips; running generators cannot be connected; the line-up drops
- Cause
- Protection logic not tuned for a long sag signature
- Prevention in place
- Isolating breakers and generator start built into each DRUPS line-up
- Detection in place
- None before the event; the weakness showed only under this sag
- S 9
- It removed power from a significant part of an Availability Zone: 9.
- O 3
- Long sags of this shape are uncommon: 'remote to infrequent'.
- D 8
- No recorded test exercised the protection with a long sag.
Corrective action
- Additional breakers to break from degraded utility power faster (AWS, committed) Correction of errors #1
After action: S9 · O2 · D6 → RPN 108. Faster isolation addresses the mechanism directly. AWS has not reported completion, so this is a claim about the action, not a measured result.
Who acts — playbook
- Authorised electrical person Test UPS input isolation against long-sag profiles, not only a clean loss of supplyNFPA 110Lesson #2
- Authorised electrical person Alarm on flywheel speed falling while the input breaker is still closedUptime OSContributing factor #2
- Operations lead Fail control-plane services away from the zone as soon as a line-up dropsSRE incident mgmtCorrection of errors #5
- Authorised electrical person Re-engage line-ups by hand only after on-site checks show it is safeNFPA 70ECorrection of errors #1
- Service recovery lead Restart instances in order once both line-ups are proven stableSRE incident mgmtCorrection of errors #6
Evidence
- Sequence of events #3“fail to open quickly enough”
- Contributing factor #2The breakers isolating the DRUPS from the utility did not open quickly enough, and the flywheel energy drained into the grid (AWS summary).
- Reference #1 · official-postmortem“failed to open quickly enough”
FM-02 Both line-ups fail together because they share the same DRUPS design and weaknessDual power line-ups of one design 9·3·7 189 —
- Function
- Keep each instance powered if either line-up fails
- Effect
- Instances lose primary and secondary power at once
- Cause
- Common-mode design across the redundant paths
- Prevention in place
- Two independent line-ups per instance
- Detection in place
- None recorded; common-mode risk is not visible in normal operation
- S 9
- It defeats the redundancy that protects every instance: 9.
- O 3
- Requires a grid event that hits the shared weakness: 'remote to infrequent'.
- D 7
- Common-mode weaknesses do not show in normal running or simple failover tests.
Corrective action
- Additional breakers on the line-ups (AWS, committed) Correction of errors #1
Who acts — playbook
- Authorised electrical person Review redundant power paths for shared designs that one grid event can defeat togetherUptime OSLesson #1
- Operations lead Alert when both feeds to a rack group drop within the same secondUptime OSContributing factor #3
- Service recovery lead Move customer launches to unaffected zones while power is outSRE incident mgmtCorrection of errors #5
- Communications lead Tell customers which zone failed and that multi-zone workloads are unaffectedITIL 4Lesson #6
Evidence
- Sequence of events #4“affected instances lose both their primary and secondary power”
- Contributing factor #3Both power line-ups used the same DRUPS design, so the same sag defeated them together and instances lost primary and secondary power (AWS summary).
- Root cause“both line-ups were lost together”
FM-03 A latent bug stops automatic recovery of part of the fleetInstance recovery software 6·4·7 168 72
- Function
- Bring all instances back automatically when power returns
- Effect
- The remaining instances need manual recovery over several hours
- Cause
- Recovery path rarely exercised at scale
- Prevention in place
- Automated recovery workflows
- Detection in place
- Visible only when a mass recovery ran
- S 6
- It stretched the outage from about 2.5 hours for most customers to about 9.5 hours for the rest: 6.
- O 4
- Mass recoveries are rare, but each one can expose such bugs: 'infrequent'.
- D 7
- Nothing exercised the path before the event.
Corrective action
- Fix the latent bug (AWS, in testing) Correction of errors #2
- Regular recovery tests on unoccupied long-running hosts (AWS, committed) Correction of errors #3
After action: S6 · O3 · D4 → RPN 72. Regular recovery testing is aimed exactly at detection; the bug fix lowers occurrence. Neither is reported complete.
Who acts — playbook
- Service recovery lead Run recovery workflows on spare long-running hosts on a scheduleSRE incident mgmtCorrection of errors #3
- Operations lead Track the share of instances recovered automatically and alert when it stallsSRE incident mgmtLesson #4
- Service recovery lead Switch to manual recovery for instances the automation cannot restoreITIL 4Correction of errors #6
- Communications lead Give affected customers a per-instance recovery statusITIL 4Lesson #4
On the record at this failure
Evidence
- Sequence of events #15“A latent bug in the instance management software”
- Contributing factor #4A latent bug in the instance management software blocked automatic recovery of part of the fleet (AWS summary).
- Metric #6Nearly all instances recovered: 08:00 PDT, 9 hours 35 minutes after the trigger
FM-05 Launch and scaling calls fail until the APIs are failed away from the degraded zone by handInstance launch APIs 6·4·4 96 72
- Function
- Let customers launch and scale in healthy zones during a zone failure
- Effect
- Customers cannot launch or scale for about 77 minutes; later, stale state confuses them
- Cause
- Control-plane dependence on the failed zone; slow propagation of state after recovery
- Prevention in place
- Regional APIs spanning several zones
- Detection in place
- Customer-visible errors
- S 6
- It blocks the workaround customers need (launch elsewhere): 6.
- O 4
- Any zone failure tests this dependency: 'infrequent'.
- D 4
- Errors were visible, but the response was manual.
Corrective action
- More resilient launch APIs, Sydney roll-out planned for July 2016 (AWS) Correction of errors #4
After action: S6 · O3 · D4 → RPN 72. API changes target the dependency; completion is not reported.
Who acts — playbook
- Operations lead Design regional APIs so they shed a failed zone automaticallySRE incident mgmtCorrection of errors #4
- Operations lead Alert on launch error rate per zone, not only per regionSRE incident mgmtContributing factor #6
- Service recovery lead Fail launches away from the degraded zone at onceSRE incident mgmtCorrection of errors #5
- Communications lead Warn customers that resource state may lag while the APIs catch upITIL 4Lesson #5
On the record at this failure
Evidence
- Sequence of events #6“Customers get errors when launching new instances”
- Sequence of events #8“manual failover away from degraded services”
- Contributing factor #6Instance launch APIs depended on the degraded zone until the team failed them away by hand (AWS summary).
FM-04 Hard drives fail on several storage servers; volumes with both replicas on failed servers cannot be restored automaticallyEBS storage servers 7·2·5 70 —
- Function
- Keep volume data durable through a power loss
- Effect
- A very small share of volumes stays out much longer; some data is at risk
- Cause
- Drive failures in the power event, with both replicas on failed hardware
- Prevention in place
- Replication of each volume to multiple servers in the zone
- Detection in place
- Found during recovery
- S 7
- Possible data loss for the affected volumes is serious even at a small share: 7.
- O 2
- Under 0.01% of volumes: 'remote'.
- D 5
- The replication system knows replica health, but the double loss was found only in recovery.
Corrective action
- None published — residual risk.
Who acts — playbook
- Service recovery lead List volumes whose replicas are all on failed servers as soon as power returnsNIST SP 800-34Contributing factor #5
- Service recovery lead Prioritise manual repair of the storage servers that hold the only copiesNIST SP 800-34Correction of errors #6
- Communications lead Tell owners of affected volumes early and point them to their snapshotsITIL 4Contributing factor #5
- Operations lead Restore from snapshots where a server cannot be repairedISO 22301Lesson #6
Evidence
- Sequence of events #16“storage servers suffered failed hard drives”
- Metric #7EBS volumes not automatically recoverable: under 0.01% of the zone's volumes
- Contributing factor #5Some storage servers lost hard drives in the event; volumes with both replicas on failed servers could not be restored automatically (AWS summary).
Scoring rubric and method
Scales adapted from IEC 60812:2018 and AIAG-VDA. RPN = S × O × D. High: S ≥ 9 with O ≥ 4 or D ≥ 7, or RPN ≥ 300. Medium: RPN ≥ 120 or S ≥ 7. Severity overrides the product: 9 × 2 × 9 = 162 would otherwise hide a region-wide outage nothing could catch. Quotes are checked verbatim against this dossier; a revised score needs a published action. RZ analyst assessment, not an operator document.
Severity
| 10 | Hazard to people, or loss of the facility / several regions |
| 9 | Region-wide or provider-wide outage of a foundational service, no workaround |
| 8 | Full outage of a major service for hours |
| 7 | Major degradation of a major service |
| 6 | Partial outage confined to one zone or one service |
| 5 | Customer-visible degradation |
| 4 | Limited customer impact |
| 3 | Internal impact only |
| 2 | Negligible |
| 1 | No effect |
Occurrence
| 10 | Near certain: the cause is present in normal operation |
| 8 | Frequent: routine work exercises the cause |
| 6 | Occasional: a foreseeable slip or condition, weakly guarded |
| 4 | Infrequent: needs an unusual combination |
| 2 | Remote: guarded by design |
| 1 | Eliminated by design |
Detection
| 10 | No control could detect it |
| 9 | Detected only through customer impact |
| 8 | Detected after impact by internal monitoring |
| 6 | Detected at onset, not prevented |
| 4 | Detected before impact with time to act |
| 2 | Automated interlock almost certainly stops it |
| 1 | Certain to be stopped |
Root cause and contributing factors
Full root-cause narrative
Contributing factors by category
- The grid fault was a long voltage sag, not a clean outage, so it did not trip the protection the way a dead feed would (AWS summary).
- The breakers isolating the DRUPS from the utility did not open quickly enough, and the flywheel energy drained into the grid (AWS summary).
- Both power line-ups used the same DRUPS design, so the same sag defeated them together and instances lost primary and secondary power (AWS summary).
- A latent bug in the instance management software blocked automatic recovery of part of the fleet (AWS summary).
- Some storage servers lost hard drives in the event; volumes with both replicas on failed servers could not be restored automatically (AWS summary).
- Instance launch APIs depended on the degraded zone until the team failed them away by hand (AWS summary).
- Internal DNS hosts were overloaded by the recovery load after power returned (AWS summary).
Analysis
A sag, not a blackout
A dead feed is the easy case for protection. A long sag leaves enough voltage that the input breaker logic hesitates, and a flywheel UPS has only seconds of energy to spend. The design worked well for years and failed on a waveform it had not been built for.
Common-mode failure across two line-ups
Every instance had two independent line-ups. Both used the same DRUPS scheme, so the same sag defeated both. Redundancy counts only against failures that do not hit every copy the same way.
The long tail was software
Power returned 81 minutes after the trigger, but nearly all instances were back only after about nine and a half hours. DNS load, slow API state, a latent recovery bug and storage drive failures each added time.
Multi-zone design held
AWS notes that customers running across several Availability Zones kept their applications available. The event is a clear case for spreading critical workloads across zones.
What the summary does not say
It does not name the facility, the DRUPS make, the breaker type, how many instances were affected or the cost. It also does not report when the added breakers were installed.
Technical deep-dive
Corrective actions and lessons
Correction of errors
| Action | Owner | Status |
|---|---|---|
| Add breakers so connections to degraded utility power are broken faster and generators engage before the UPS energy is used up | AWS | Committed (completion not reported) |
| Fix the latent bug that stopped automatic recovery of some instances | AWS | In testing at the time of the summary; deployment over the following days |
| Start a program to test recovery processes regularly on unoccupied long-running hosts | AWS | Committed (completion not reported) |
| Make the instance launch APIs more resilient to a zone failure, with roll-out to the Sydney Region in July 2016 | AWS | Planned for July 2016 (completion not reported) |
| Manual failover of launch APIs away from the degraded zone | AWS | Done during the event, 23:42 PDT |
| Manual recovery of the remaining instances and of damaged storage servers | AWS | Done during the event |
Lessons learnt
- Two power line-ups are only independent if they fail in different ways. Same DRUPS design on both sides means one grid signature can take both.
- Protection must be tested against the grid's real failure shapes, including long sags, not only a clean loss of supply.
- A rotary UPS has seconds of stored energy; anything that lets that energy leak back into the grid turns ride-through into a trip.
- Mass recovery after a power loss exercises code paths that daily operation never touches; test them deliberately and often.
- Control-plane APIs must not depend on the zone that has failed; failing them away by hand cost over an hour of launch errors.
- Customers running across several Availability Zones stayed up; single-zone workloads carried the whole outage.
Improvements
- Designadditional breakers to isolate degraded utility power faster (AWS committed).
- Software: fix the latent instance-recovery bug (AWS, in testing at the time).
- Processregular recovery tests on unoccupied long-running hosts (AWS committed).
- Control plane: more resilient launch APIs, Sydney roll-out planned for July 2016 (AWS).
- Analyst recommendation (not in the summary): test UPS isolation logic against recorded sag profiles from the local grid, and avoid identical protection designs on both line-ups.
References and provenance
- official-postmortem AWS Post-Event Summary: Summary of the AWS Service Event in the Sydney Region“a set of breakers responsible for isolating the DRUPS from utility power failed to open quickly enough”https://aws.amazon.com/message/4372T8/
- vendor-status AWS Post-Event Summaries index“Summary of the AWS Service Event in the Sydney Region”https://aws.amazon.com/premiumsupport/technology/pes/
Quotes are short, attributed, and for provenance only; the analysis is original. Last verified 2026-11-11.