Digital Realty Singapore Lithium-Ion UPS Fire (2024)
Summary
A lithium-ion UPS battery fire at a Singapore data center forced an emergency power shutdown, disrupting customers including Alibaba and Lazada — another instance of Li-ion UPS risk in modern facilities.
- Users affected
- Cloud/e-commerce customers incl. Alibaba/Lazada in the region
- Duration
- Alarm morning 10 Sep, AZ-C offline ~01:46 11 Sep; no restoration time in dossier.
- Financial
- Not published
- Scope
- Li-ion UPS fire, emergency power-off
- Site
- Digital Realty Singapore data center · Singapore, Singapore
- Services down
- Alibaba/Lazada regional services (reported), Colocation customers
How the defences failed
Li-ion UPS fire forced emergency power shutdown, impacting customers incl. Alibaba/Lazada — sub-scores ESTIMATED from public impact reporting, pending deep research.
All 10 impact metrics
| Fire date | 10 Sep 2024 (morning SGT) |
| Occupants self-evacuated before firefighters arrived | ~20 people |
| Injuries | 0 (all personnel out by ~08:15 SGT) |
| SCDF water jets deployed | 4 water jets |
| Unmanned firefighting robots deployed | 1 (damping-down phase) |
| Alarm to emergency power shutdown | ~18 hours (DCD reconstruction; ~01:46, 11 Sep) |
| Total operation duration to 'stable' | ~10 Sep to 12 Sep (~2 days) |
| Facility | ~17,000 sqm, 4 stories, launched 2016 |
| Battery-room location vs 2020 SCDF ESS standard | 3rd-floor mezzanine vs required ground floor |
| Tenants/services disrupted | Alibaba Cloud Singapore AZ-C, Lazada, ByteDance/TikTok |
Sequence of events
- TRIGGER Electrical fault in a third-floor mezzanine battery room initiates Li-ion thermal runaway at the Digital Realty Digital Loyang data center, Loyang, Singapore. 'Early investigations suggest an electrical issue in one of the battery rooms triggered the blaze.'
- DETECTION Building fire-alarm system activates — the first publicly indicated detection event; no discrete smoke/heat-sensor timing is disclosed beyond this alarm.
- MITIGATION Facility sprinkler systems activate over the involved battery/power rooms on the third-floor mezzanine.
- MITIGATION About 20 occupants self-evacuate the building before firefighters arrive.
- MITIGATION SCDF alerted and responds to the Loyang data centre to secure the premises and stabilise the situation.Fire & rescue commander
- MITIGATION All on-site personnel evacuated with no injuries; SCDF deploys four water jets to cool and contain the battery fire.Safety officerFire & rescue commander
- IMPACT Alibaba Cloud detects network anomalies in Singapore Availability Zone C; Lazada and ByteDance/TikTok begin experiencing service disruption.Customer
- CASCADE Alibaba warns of increasing likelihood of a complete network outage in Availability Zone C if battery-room temperatures are not controlled; O&M engineers are unable to enter the building.Communications lead
- MITIGATION SCDF firefighting knocks down / contains the blaze after roughly half a day of cooling; operation flagged as prolonged due to battery cooling requirements (exact containment time per DCD reconstruction, not re-verified this pass).
- IMPACT Firefighting and sprinkler water accumulates and leaks into server halls; Alibaba reports 'water accumulation and leaks, posing a risk of electrical short circuits.'
- CASCADE Emergency power shutdown of the affected building executed to prevent electrical short circuits from standing water — this de-energisation, not flame, takes Alibaba Cloud Availability Zone C fully offline (~01:46 per DCD, not re-verified this pass).
- MITIGATION Operation spills into a second day; an unmanned firefighting robot is deployed for damping-down as manual entry remains too hazardous/hot.Fire & rescue commander
- RECOVERY SCDF declares the site stable after multi-day cooling and damping-down operations.Fire & rescue commander
- RECOVERY BCA assesses the structure: minor plaster delamination, paint peeling and soot only, structural integrity intact; issues closure orders for portions of the third, fourth floors and mezzanine.Authority / investigator
- RESTORED Alibaba carefully dries water-exposed hardware to ensure data security; migration and restoration of affected machinery proceeds as planned.Service recovery lead
Response by role
What each role did
Roles the sequence of events shows acting; every entry quotes its source line. Select a time to jump to it.
Role by role
Recorded actions / playbook actions per role. A role with 0 recorded actions does not appear in the sources.
Digital Realty Digital Loyang on-site staff — not named; the alarm is the only detection on record — Meets the first alarm: on-shift technician or security in a facility, on-call engineer in a service.
On the record
No action by this role appears in the sources.
Playbook analyst guidance by failure mode, not a record of what happened
- FM-04Report the point at which O&M staff can no longer enter, so tenants can plan remote shutdownSRE incident mgmt
- FM-01Treat a BMS fault or battery-room temperature alarm as a call-out; do not wait for the building fire alarmNFPA 855
- FM-03Walk the server halls under the battery rooms for leaks and report water on the floor at onceITIL 4
- FM-02Give SCDF the battery chemistry, string layout and room access route on arrivalNFPA 1561
No incident commander is named in the record — Owns every decision until formally relieved: site duty manager on scene, or the declared IC of a service incident.
On the record
No action by this role appears in the sources.
Playbook analyst guidance by failure mode, not a record of what happened
- FM-04Agree with SCDF in advance a re-entry and safe-shutdown protocol for O&M engineersImprovement #4
- FM-01Order evacuation and call SCDF at first sign of runaway, stating Li-ion in a third-floor roomNIMS / ICS
- FM-03Order the building shutdown when water threatens short circuits, and tell tenants the timeNIMS / ICS
- FM-06Preserve the battery room as evidence and log who has handled itNIMS / ICS
- FM-02Agree with SCDF the cooling plan and the water drainage route before jets are committedNIMS / ICS
- FM-05Fail over traffic out of the zone before the shutdown, not after itSRE incident mgmt
SCDF, the Singapore Civil Defence Force — External incident commander for fire, rescue and hazardous materials; works in unified command with the site.
On the record
- Responds to secure the premises and stabilise the situation
SCDF alerted and responds to the Loyang data centre
- Deploys four water jets to cool and contain the battery fire
SCDF deploys four water jets to cool and contain the battery fire
- Deploys a robot on the second day because manual entry stays too hot
an unmanned firefighting robot is deployed for damping-down
- Declares the site stable on 12 Sep after multi-day cooling
SCDF declares the site stable
Playbook analyst guidance by failure mode, not a record of what happened
- FM-02Declare stable only after cooling and damping-down confirm no re-ignitionNFPA 1561
Whoever executed the emergency power shutdown — not named — Switching, isolation and lock-out of power sources, and safe re-energisation.
On the record
No action by this role appears in the sources.
Playbook analyst guidance by failure mode, not a record of what happened
Building occupants and site staff who evacuated, about 20 before SCDF arrived — Head count, exclusion zones, PPE and the go / no-go for re-entry.
On the record
- All on-site personnel are out by about 08:15 SGT, no injuries
All on-site personnel evacuated with no injuries
Playbook analyst guidance by failure mode, not a record of what happened
Alibaba Cloud O&M engineers who dried and restored the wet hardware — Restores customer service: failover, workload moves, capacity, backlog drain.
On the record
- Dries wet hardware, then migrates and restores machinery
Alibaba carefully dries water-exposed hardware to ensure data security
Playbook analyst guidance by failure mode, not a record of what happened
- FM-05Alarm on network anomalies in one AZ and map which tenants depend on itSRE incident mgmt
- FM-04Prepare a remote or SCDF-escorted shutdown plan for tenant hardware before access is lostISO 22301
- FM-04Re-enter on release and migrate machinery in the order agreed with tenantsISO 22301
- FM-03Dry, test and re-energise halls one at a time after water is removedNFPA 75
- FM-06Take the same battery model and string layout out of other sites for inspectionNFPA 855
- FM-05Bring the zone back on release, in dependency order, and confirm with tenantsITIL 4
Alibaba Cloud, which warned of a likely full AZ-C outage — Status page, customer notices, regulators and press; one voice, timed updates.
On the record
- Warns of a complete AZ-C outage if battery-room temperatures are not controlled
Alibaba warns of increasing likelihood of a complete network outage
Playbook analyst guidance by failure mode, not a record of what happened
- FM-05Warn tenants early that the AZ may go fully offline and say what to moveSRE incident mgmt
Alibaba Cloud AZ-C and its tenants Lazada and ByteDance/TikTok — The tenant or service user: their own redundancy, backups and continuity plan.
On the record
- Alibaba Cloud, a tenant, detects network anomalies in AZ-C; Lazada and ByteDance/TikTok begin to see disruption
Alibaba Cloud detects network anomalies in Singapore Availability Zone C
Playbook analyst guidance by failure mode, not a record of what happened
- FM-05Place replicas in a second availability zone in another buildingImprovement #6
- FM-04Dry and verify wet hardware for data security before it returns to serviceNIST SP 800-34Correction of errors #4
- FM-03Power down wet racks and dry the hardware before migrationNIST SP 800-34Correction of errors #4
- FM-06Ask the operator for the battery make and chemistry and review it against your riskISO 22301
- FM-05Shift Lazada and TikTok-style downstream traffic to another AZ until the building is releasedISO 22301
BCA, the Singapore building authority, with SCDF — Regulator, investigator or court that establishes cause and obligations after the event.
On the record
- Finds structure intact and issues closure orders for parts of floors 3, 4 and the mezzanine
BCA assesses the structure
Playbook analyst guidance by failure mode, not a record of what happened
Failure mode & effects analysis (FMEA)
The physical chain at Digital Realty's Digital Loyang facility in Singapore — the lithium-ion battery bank in the third-floor mezzanine battery rooms, the fire alarm and water-based suppression, the separation between battery rooms and the server halls below, the emergency power shutdown, operator re-entry and hardware drying, and the tenant availability zone (Alibaba Cloud Singapore AZ-C) and downstream services that depended on the building. Analysed retrospectively from press reporting only (DCD, Straits Times/SCDF, The Star): there is no official post-mortem, the trigger is described only as 'an electrical issue in one of the battery rooms', and battery make, model, chemistry, age and state of charge are undisclosed. Every facility-side corrective action in this dossier is an analyst recommendation with status 'Open — no public evidence', so no revised score is claimed for any mode: all are shown as residual risk.
- Caught only after impactD ≥ 8
- 3 of 6
- Actions that cut occurrenceO lowered
- 0
- Actions that cut detectionD lowered
- 0
- Actions that cut severityblast radius unchanged
- 0
FM-04 Fire-safety protocol keeps O&M engineers out of the building, so damage assessment, controlled shutdown and drying of wet hardware are delayedOperator re-entry and hardware recovery 7·6·8 336 —
- Function
- Let tenant engineers protect, assess and restore equipment as soon as the fire allows
- Effect
- Alibaba engineers cannot enter while the battery-room temperature threatens AZ-C; wet hardware has to be dried before migration and restoration, which continues after the site is declared stable on 12 Sep
- Cause
- No pre-agreed operator re-entry or safe-shutdown protocol with SCDF is recorded
- Prevention in place
- None recorded
- Detection in place
- Found during the incident
- S 7
- This mode sets how long the tenant outage lasts after the fire rather than whether it happens: a major degradation of a major service. Scored below FM-03 so the shutdown is not counted twice.
- O 6
- Exclusion of operators during active firefighting is the normal protocol, so the condition is present in any fire of this kind and only weakly guarded: 'occasional'.
- D 8
- The lockout's effect on recovery was learned during the incident, with internal awareness but after impact.
Corrective action
- Pre-agree an operator re-entry and safe-shutdown protocol with SCDF (analyst recommendation, status not disclosed) Improvement #4
- Dry, assess and restore water-exposed hardware — in progress for this incident; a recovery step, not a preventive control Correction of errors #4
Who acts — playbook
- Incident commander Agree with SCDF in advance a re-entry and safe-shutdown protocol for O&M engineersImprovement #4
- First responder Report the point at which O&M staff can no longer enter, so tenants can plan remote shutdownSRE incident mgmt
- Service recovery lead Prepare a remote or SCDF-escorted shutdown plan for tenant hardware before access is lostISO 22301
- Fire & rescue commander Escort named O&M engineers to shut down specific racks when the area is safeNFPA 1561
- Customer Dry and verify wet hardware for data security before it returns to serviceNIST SP 800-34Correction of errors #4
- Service recovery lead Re-enter on release and migrate machinery in the order agreed with tenantsISO 22301
On the record at this failure
- Communications lead Warns of a complete AZ-C outage if battery-room temperatures are not controlled
- Fire & rescue commander Declares the site stable on 12 Sep after multi-day cooling
- Service recovery lead Dries wet hardware, then migrates and restores machinery
Evidence
- Sequence of events #82024-09-10 daytime — Alibaba warns of increasing likelihood of a complete network outage in Availability Zone C if battery-room temperatures are not controlled; O&M engineers are unable to enter the building.
- Contributing factor #4Firefighting-protocol lockout of operators: Alibaba's operation-and-maintenance engineers were unable to enter the building, delaying damage assessment, drying and restoration of water-exposed hardware (DCD).
- Sequence of events #15post-stabilisation (Sep 2024) — Alibaba carefully dries water-exposed hardware to ensure data security; migration and restoration of affected machinery proceeds as planned.
- Sequence of events #132024-09-12 — SCDF declares the site stable after multi-day cooling and damping-down operations.
FM-01 An electrical fault in one battery room initiates lithium-ion thermal runawayLi-ion battery bank and battery-room electrical system (third-floor mezzanine) 10·4·8 320 —
- Function
- Store backup energy for the UPS without an electrical fault developing into a fire
- Effect
- Battery fire in an occupied building; about 20 occupants self-evacuate and all personnel are out by about 08:15 SGT with no injuries; the fire leads to a multi-day firefighting operation and an emergency power shutdown of the building
- Cause
- Undisclosed. Press relaying SCDF reports only 'an electrical issue in one of the battery rooms'; whether it was a cell short, a charger/BMS fault or a connection arc is not public, and no maintenance or inspection lapse is identified
- Prevention in place
- None recorded; the battery make, chemistry, age and any inspection regime are not disclosed
- Detection in place
- Building fire-alarm activation is the first publicly indicated detection event; no earlier warning of the electrical fault is disclosed
- S 10
- A fire in an occupied building that also takes the whole facility out of service for days is the rubric's 10, which it reserves for hazard to people or loss of a facility. The evacuation worked and no injuries are recorded, but the hazard was real.
- O 4
- An electrical fault developing into thermal runaway needs an unusual combination, so 'infrequent'. Held at 4 rather than higher because the dossier identifies no lapse that would make it routine; the cause itself is undisclosed.
- D 8
- The first disclosed detection is the fire alarm, after the fault had already become a fire, so 'detected after impact by internal monitoring'. Whether any battery monitoring existed is not public.
Corrective action
- Battery-room electrical-integrity monitoring (BMS fault logging, connection and thermal inspection, state-of-charge and cell-age tracking) — analyst recommendation, status not disclosed Improvement #5
- Root-cause investigation of the battery-room electrical fault — early investigation only, findings not public Correction of errors #6
Who acts — playbook
- Authorised electrical person Log BMS faults and inspect battery connections thermally; track state of charge and cell age per stringImprovement #5
- First responder Treat a BMS fault or battery-room temperature alarm as a call-out; do not wait for the building fire alarmNFPA 855
- Authorised electrical person Open the DC isolator of the faulted battery string and keep the other strings separatedNFPA 855
- Incident commander Order evacuation and call SCDF at first sign of runaway, stating Li-ion in a third-floor roomNIMS / ICS
- Safety officer Account for every occupant at the assembly point and report the count to SCDFNIMS / ICS
- Authority / investigator Establish the fault mechanism and battery make, chemistry and age, and publish themCorrection of errors #6
Evidence
- Sequence of events #12024-09-10 morning SGT — Electrical fault in a third-floor mezzanine battery room initiates Li-ion thermal runaway at the Digital Realty Digital Loyang data center, Loyang, Singapore. 'Early investigations suggest an electrical issue in one of the battery rooms triggered the blaze.'
- Reference #1 · press“Early investigations suggest an electrical issue in one of the battery rooms triggered the blaze.”
- Sequence of events #22024-09-10 morning SGT — Building fire-alarm system activates — the first publicly indicated detection event; no discrete smoke/heat-sensor timing is disclosed beyond this alarm.
- Metric #2Occupants self-evacuated before firefighters arrived: ~20 people
- Metric #3Injuries: 0 (all personnel out by ~08:15 SGT)
- Contributing factor #6No public evidence of a maintenance/inspection/testing lapse: the trigger is described only as 'an electrical issue in one of the battery rooms,' with battery make/model, chemistry, age and state of charge undisclosed — an evidentiary gap rather than a confirmed clean bill (Straits Times/SCDF).
FM-03 Firefighting and sprinkler water drains from the third-floor battery rooms into the server halls, forcing an emergency power shutdown of the buildingSeparation between battery rooms and server halls (siting, bunding, drainage) 9·4·6 216 —
- Function
- Keep suppression water from a battery-room fire away from energised IT equipment
- Effect
- Water accumulates and leaks into server rooms with a risk of short circuits; the affected building is de-energised in the early hours of 11 Sep, about 18 hours after the alarm, which takes Alibaba Cloud Singapore AZ-C fully offline
- Cause
- Battery rooms sited above grade on the third-floor mezzanine within the same structure as the server halls, with no water-tight separation. The 2016 facility predates SCDF's 2020 standard requiring ground-floor ESS rooms, so the siting was grandfathered rather than a breach (Digital Realty's position, per DCD)
- Prevention in place
- None recorded; no bunding or drainage between battery rooms and IT space is described
- Detection in place
- Alibaba reported water accumulation and leaks in the server room before the shutdown
- S 9
- This is the route by which a battery fire became a de-energised building and a full availability-zone outage with downstream tenants: the rubric's 9 for an outage with no workaround inside the facility. Not 10, because FM-01 already carries the facility loss and no hazard to people arises from this step.
- O 4
- A standing design condition, but it is exercised only when suppression water is discharged in the battery rooms in volume, which needs a fire first: 'infrequent'.
- D 6
- The water ingress was seen while it happened and there were hours before the shutdown, but nothing could stop the water once it was flowing, so 'detected at onset, not prevented'.
Corrective action
- Relocate or segregate Li-ion ESS battery rooms to ground-floor, water-contained enclosures per the SCDF 2020 ESS standard — status 'Open — no public completion evidence' Correction of errors #1
- Install water-tight bunding and drainage between battery rooms and server halls — status 'Open — no public evidence' Correction of errors #2
Who acts — playbook
- Safety officer Add water-tight bunding and drainage between battery rooms and IT hallsCorrection of errors #2
- First responder Walk the server halls under the battery rooms for leaks and report water on the floor at onceITIL 4
- Authorised electrical person Open the feeders of halls where water is dripping or pooled before the water reaches live equipmentNFPA 70EContributing factor #3
- Incident commander Order the building shutdown when water threatens short circuits, and tell tenants the timeNIMS / ICS
- Service recovery lead Dry, test and re-energise halls one at a time after water is removedNFPA 75
- Customer Power down wet racks and dry the hardware before migrationNIST SP 800-34Correction of errors #4
Evidence
- Sequence of events #102024-09-10 overnight to 2024-09-11 — Firefighting and sprinkler water accumulates and leaks into server halls; Alibaba reports 'water accumulation and leaks, posing a risk of electrical short circuits.'
- Sequence of events #112024-09-11 early hours SGT — Emergency power shutdown of the affected building executed to prevent electrical short circuits from standing water — this de-energisation, not flame, takes Alibaba Cloud Availability Zone C fully offline (~01:46 per DCD, not re-verified this pass).
- Metric #6Alarm to emergency power shutdown: ~18 hours (DCD reconstruction; ~01:46, 11 Sep)
- Metric #9Battery-room location vs 2020 SCDF ESS standard: 3rd-floor mezzanine vs required ground floor
- Contributing factor #1Legacy above-grade battery siting: Li-ion energy-storage rooms were on the third-floor mezzanine, contrary to SCDF's 2020 standard requiring ground-floor placement. Digital Realty states the 2016 facility predated the rule, so it was grandfathered — but the elevated siting is the single largest aggravating design factor (DCD).
- Contributing factor #3Vertical co-location of burning batteries above live server halls: with no water-tight separation between the third-floor battery rooms and IT space, suppression water accumulated and leaked into server rooms, creating the short-circuit risk that drove the emergency shutdown (DCD; Alibaba via DCD).
- Technical deep-dive“This de-energisation, not flame, is what took Alibaba Cloud Singapore Availability Zone C fully offline”
FM-06 Only an early finding is public; the fault mechanism and battery details remain undisclosedRoot-cause investigation and public disclosure 4·6·9 216 —
- Function
- Establish and publish the fault, battery make, chemistry and age so operators of similar battery rooms can act
- Effect
- Customers and other operators cannot tell whether the ignition cause exists elsewhere; this dossier cannot rule a maintenance lapse in or out
- Cause
- SCDF / Digital Realty investigation findings not publicly disclosed as of this review
- Prevention in place
- None recorded
- Detection in place
- Visible only as the absence of findings
- S 4
- The missing findings do not stop a service; they limit what others can do to protect themselves: 'limited customer impact'.
- O 6
- The dossier records only an early investigation with findings not disclosed, a foreseeable condition with nothing requiring publication: 'occasional'.
- D 9
- Nothing surfaces the gap except its absence, which customers notice only from outside.
Corrective action
- None published — residual risk.
Who acts — playbook
- Authority / investigator Publish SCDF and operator findings on the fault, battery make, chemistry and ageCorrection of errors #6
- Safety officer Keep battery-room monitoring and inspection records so a lapse can be confirmed or excludedImprovement #5
- Incident commander Preserve the battery room as evidence and log who has handled itNIMS / ICS
- Service recovery lead Take the same battery model and string layout out of other sites for inspectionNFPA 855
- Customer Ask the operator for the battery make and chemistry and review it against your riskISO 22301
Evidence
- Correction of errors #6Root-cause investigation of the battery-room electrical fault (make/model/chemistry/age) (Early investigation only — findings not publicly disclosed (Straits Times))
- Contributing factor #6No public evidence of a maintenance/inspection/testing lapse: the trigger is described only as 'an electrical issue in one of the battery rooms,' with battery make/model, chemistry, age and state of charge undisclosed — an evidentiary gap rather than a confirmed clean bill (Straits Times/SCDF).
- Root cause“No make/model/chemistry can be attributed without over-claiming.”
FM-02 Water suppression cools but cannot stop cell-to-cell thermal-runaway propagation, so the fire persists and the operation runs over two daysBattery-room fire suppression (facility sprinklers and SCDF water jets) 8·4·6 192 —
- Function
- Extinguish a battery-room fire quickly and with as little water as possible
- Effect
- Sprinklers and four SCDF water jets are needed; containment takes about half a day, an unmanned firefighting robot is used for damping-down on the second day, and the site is declared stable only on 12 Sep; the operation produces the water volume that later reaches the server halls
- Cause
- Water is the only firefighting medium recorded for the battery rooms, and it removes heat without arresting self-sustaining Li-ion propagation; the above-grade siting also complicated firefighter access and cooling
- Prevention in place
- Facility sprinkler systems over the battery and power rooms
- Detection in place
- The persistence of the fire was visible to responders from the start of firefighting
- S 8
- This mode sets the duration and the water load of the event rather than its existence; days of firefighting that keep the facility out of reach is the rubric's 8. Not scored at 10 so the fire is not counted twice at full weight with FM-01.
- O 4
- It needs a battery-room fire first, which is infrequent; given such a fire, water-only suppression would behave the same way.
- D 6
- Responders could see at once that water was only cooling the batteries, but nothing in place could prevent the propagation: 'detected at onset, not prevented'.
Corrective action
- Deploy thermal-runaway-appropriate detection and suppression (cell-level, gas or aerosol) to shorten cooling and cut water volume — status 'Open — no public evidence' Correction of errors #3
- Supplement or replace water-only suppression in Li-ion battery rooms (analyst recommendation) Improvement #3
Who acts — playbook
- Safety officer Fit thermal-runaway detection and gas or aerosol suppression to Li-ion rooms to shorten cooling and cut water volumeNFPA 855Correction of errors #3
- First responder Give SCDF the battery chemistry, string layout and room access route on arrivalNFPA 1561
- Fire & rescue commander Cool the battery rooms continuously with water jets and a robot, accepting a multi-day operationNFPA 855
- Incident commander Agree with SCDF the cooling plan and the water drainage route before jets are committedNIMS / ICS
- Fire & rescue commander Declare stable only after cooling and damping-down confirm no re-ignitionNFPA 1561
- Authorised electrical person Keep battery rooms de-energised and under temperature watch until released by SCDFNFPA 855
On the record at this failure
Evidence
- Sequence of events #32024-09-10 morning SGT — Facility sprinkler systems activate over the involved battery/power rooms on the third-floor mezzanine.
- Metric #4SCDF water jets deployed: 4 water jets
- Sequence of events #122024-09-11 second day — Operation spills into a second day; an unmanned firefighting robot is deployed for damping-down as manual entry remains too hazardous/hot.
- Metric #7Total operation duration to 'stable': ~10 Sep to 12 Sep (~2 days)
- Contributing factor #2Water-based suppression against Li-ion thermal runaway: sprinklers plus four SCDF water jets could only cool, not stop, self-sustaining cell-to-cell propagation, forcing a multi-day operation and generating the water volume that later reached the IT halls (Straits Times/SCDF).
- Technical deep-dive“water is a coolant, not an extinguishant, for Li-ion thermal runaway”
FM-05 The availability zone depends on one building, so one battery-room fire takes it offline and the outage reaches downstream servicesTenant availability-zone isolation (Alibaba Cloud Singapore AZ-C and downstream services) 7·4·6 168 —
- Function
- Keep a cloud availability zone and the services built on it running through the loss of one building
- Effect
- Alibaba detects network anomalies in AZ-C on 10 Sep and the zone goes fully offline at the shutdown; Lazada and ByteDance/TikTok are disrupted
- Cause
- Single-facility concentration: the zone and its downstream tenants had insufficient isolation from a single building event
- Prevention in place
- None recorded
- Detection in place
- Alibaba detected network anomalies in AZ-C and warned of a likely complete outage
- S 7
- One availability zone of one provider is the rubric's 6, raised to 7 because the outage reached Lazada and ByteDance/TikTok as well: major degradation, not a region-wide outage.
- O 4
- It needs the loss of the building first, which is infrequent; the concentration itself is a standing condition.
- D 6
- Alibaba saw the network anomalies and warned of a complete outage hours before the shutdown, but Lazada and ByteDance/TikTok were already disrupted on 10 Sep, so 'detected at onset, not prevented'. The dossier does not record whether workloads were moved in that window.
Corrective action
- Improve tenant availability-zone isolation so a single-building event cannot take an entire zone offline (analyst recommendation, status not disclosed) Improvement #6
Who acts — playbook
- Customer Place replicas in a second availability zone in another buildingImprovement #6
- Service recovery lead Alarm on network anomalies in one AZ and map which tenants depend on itSRE incident mgmt
- Communications lead Warn tenants early that the AZ may go fully offline and say what to moveSRE incident mgmt
- Incident commander Fail over traffic out of the zone before the shutdown, not after itSRE incident mgmt
- Service recovery lead Bring the zone back on release, in dependency order, and confirm with tenantsITIL 4
- Customer Shift Lazada and TikTok-style downstream traffic to another AZ until the building is releasedISO 22301
On the record at this failure
- Customer Alibaba Cloud, a tenant, detects network anomalies in AZ-C; Lazada and ByteDance/TikTok begin to see disruption
- Communications lead Warns of a complete AZ-C outage if battery-room temperatures are not controlled
Evidence
- Sequence of events #72024-09-10 daytime — Alibaba Cloud detects network anomalies in Singapore Availability Zone C; Lazada and ByteDance/TikTok begin experiencing service disruption.
- Sequence of events #82024-09-10 daytime — Alibaba warns of increasing likelihood of a complete network outage in Availability Zone C if battery-room temperatures are not controlled; O&M engineers are unable to enter the building.
- Metric #10Tenants/services disrupted: Alibaba Cloud Singapore AZ-C, Lazada, ByteDance/TikTok
- Contributing factor #5Single-facility concentration risk for tenants: Alibaba Cloud Singapore Availability Zone C, and downstream Lazada and ByteDance/TikTok, had insufficient isolation from a single building event, so one battery-room fire produced a multi-tenant regional outage (DCD; The Star).
- Reference #3 · press“Alibaba Cloud services in Singapore, along with Lazada and ByteDance-owned TikTok, were disrupted”
Scoring rubric and method
Scales adapted from IEC 60812:2018 and AIAG-VDA. RPN = S × O × D. High: S ≥ 9 with O ≥ 4 or D ≥ 7, or RPN ≥ 300. Medium: RPN ≥ 120 or S ≥ 7. Severity overrides the product: 9 × 2 × 9 = 162 would otherwise hide a region-wide outage nothing could catch. Quotes are checked verbatim against this dossier; a revised score needs a published action. RZ analyst assessment, not an operator document.
Severity
| 10 | Hazard to people, or loss of the facility / several regions |
| 9 | Region-wide or provider-wide outage of a foundational service, no workaround |
| 8 | Full outage of a major service for hours |
| 7 | Major degradation of a major service |
| 6 | Partial outage confined to one zone or one service |
| 5 | Customer-visible degradation |
| 4 | Limited customer impact |
| 3 | Internal impact only |
| 2 | Negligible |
| 1 | No effect |
Occurrence
| 10 | Near certain: the cause is present in normal operation |
| 8 | Frequent: routine work exercises the cause |
| 6 | Occasional: a foreseeable slip or condition, weakly guarded |
| 4 | Infrequent: needs an unusual combination |
| 2 | Remote: guarded by design |
| 1 | Eliminated by design |
Detection
| 10 | No control could detect it |
| 9 | Detected only through customer impact |
| 8 | Detected after impact by internal monitoring |
| 6 | Detected at onset, not prevented |
| 4 | Detected before impact with time to act |
| 2 | Automated interlock almost certainly stops it |
| 1 | Certain to be stopped |
Root cause and contributing factors
Full root-cause narrative
Contributing factors by category
- Legacy above-grade battery siting: Li-ion energy-storage rooms were on the third-floor mezzanine, contrary to SCDF's 2020 standard requiring ground-floor placement. Digital Realty states the 2016 facility predated the rule, so it was grandfathered — but the elevated siting is the single largest aggravating design factor (DCD).
- Water-based suppression against Li-ion thermal runaway: sprinklers plus four SCDF water jets could only cool, not stop, self-sustaining cell-to-cell propagation, forcing a multi-day operation and generating the water volume that later reached the IT halls (Straits Times/SCDF).
- Vertical co-location of burning batteries above live server halls: with no water-tight separation between the third-floor battery rooms and IT space, suppression water accumulated and leaked into server rooms, creating the short-circuit risk that drove the emergency shutdown (DCD; Alibaba via DCD).
- Firefighting-protocol lockout of operators: Alibaba's operation-and-maintenance engineers were unable to enter the building, delaying damage assessment, drying and restoration of water-exposed hardware (DCD).
- Single-facility concentration risk for tenants: Alibaba Cloud Singapore Availability Zone C, and downstream Lazada and ByteDance/TikTok, had insufficient isolation from a single building event, so one battery-room fire produced a multi-tenant regional outage (DCD; The Star).
- No public evidence of a maintenance/inspection/testing lapse: the trigger is described only as 'an electrical issue in one of the battery rooms,' with battery make/model, chemistry, age and state of charge undisclosed — an evidentiary gap rather than a confirmed clean bill (Straits Times/SCDF).
Analysis
A thermal-runaway fire, but a water-caused outage
The September 2024 fire at Digital Realty's Digital Loyang facility is best understood as two coupled events. The first was a lithium-ion battery fire on the third-floor mezzanine, triggered by an electrical fault and sustained by cell-to-cell thermal runaway that water can cool but not extinguish. The second — and the one that actually caused the customer-visible outage — was hydraulic: accumulated sprinkler and firefighting water draining down into server halls, forcing an emergency power shutdown to avoid short circuits. Flame never breached the IT space or structural integrity; the suppressant did the damage.
Above-grade battery siting as the systemic root
The decisive design condition was that an energy-storage hazard sat above live server halls with no water-tight separation. SCDF's 2020 ESS standard requires Li-ion battery rooms on the ground floor precisely to avoid this geometry; the failed rooms were on the third-floor mezzanine. Gravity did the rest — water migrated down onto energised equipment. Ground-floor siting with bunded, drained containment would have decoupled the battery event from the IT load.
Legacy compliance versus safe design
Digital Realty's stated position is that the facility launched in 2016, before the 2020 standard, so the elevated placement was grandfathered rather than a breach. That is legally coherent but operationally cautionary: the arrangement that was permissible under the older code is exactly the arrangement that turned a contained battery fire into a regional cloud outage. Grandfathered compliance is not evidence of safe design.
The multi-tenant cascade
Because a single building hosted Alibaba Cloud Singapore Availability Zone C, the emergency de-energisation propagated outward — first to Alibaba's own AZ-C, then to downstream tenants Lazada and ByteDance/TikTok. The blast radius demonstrates that logical availability-zone labels do not guarantee physical isolation when redundancy is concentrated in one structure. Recovery was further slowed by fire-safety protocol barring O&M engineers from re-entry until the site was declared stable.
Evidentiary gaps that remain open
The public record does not disclose the battery/UPS make and model, cell chemistry, age, state of charge, or the precise electrical fault. The trigger is described only as 'an electrical issue in one of the battery rooms.' No maintenance, inspection or hot-work lapse is identified — which is an absence of evidence, not a clean bill. A full root cause would require the undisclosed SCDF/Digital Realty investigation findings, which were not public as of this review.
Technical deep-dive
Corrective actions and lessons
Correction of errors
| Action | Owner | Status |
|---|---|---|
| Relocate/segregate Li-ion ESS battery rooms to ground-floor, water-contained enclosures per SCDF 2020 ESS standard | Digital Realty (facility engineering) | Open — no public completion evidence |
| Install water-tight bunding/drainage between battery rooms and server halls to prevent suppression-water ingress into IT space | Digital Realty (design/build) | Open — no public evidence |
| Deploy thermal-runaway-appropriate detection and suppression (cell-level/gas/aerosol) to shorten cooling and cut water volume | Digital Realty with SCDF guidance | Open — no public evidence |
| Dry, assess and restore water-exposed hardware to ensure data security | Alibaba Cloud O&M | In progress — migration and restoration reported proceeding as planned (DCD) |
| Building-integrity assessment and closure orders for affected floors | BCA / SCDF | Completed — structural integrity intact; closure orders issued (BCA/Straits Times) |
| Root-cause investigation of the battery-room electrical fault (make/model/chemistry/age) | SCDF / Digital Realty | Early investigation only — findings not publicly disclosed (Straits Times) |
Lessons learnt
- Against Li-ion thermal runaway, water suppresses nothing — it only cools; sprinklers and four water jets could not stop cell-to-cell propagation, turning the event into a multi-day cooling operation (Straits Times/SCDF).
- The suppressant became the primary weapon of collateral damage: firefighting/sprinkler water, not flame, reached the server halls and forced the emergency power shutdown that caused the actual outage (DCD; Alibaba via DCD).
- Vertical siting of an ESS hazard above IT load converts a contained battery fire into a facility-wide IT event through simple gravity-driven water migration (DCD).
- Grandfathered/legacy compliance is not the same as safe design: the 2016 above-grade battery rooms were legal because they predated the 2020 ground-floor standard, yet that very placement drove the worst consequences (DCD).
- Operator lockout under fire-safety protocol lengthens recovery — barring O&M engineers from the building delayed drying and restoration of water-exposed hardware (DCD).
- Single-building faults still cascade to whole cloud Availability Zones; tenant redundancy that shares one physical facility is insufficient isolation (DCD; The Star).
Improvements
- DesignRelocate Li-ion energy-storage systems to ground-floor, water-segregated rooms per SCDF's 2020 ESS standard so burning batteries are not sited above live server halls and suppression water cannot drain into IT space (basis: DCD siting finding).
- DesignIntroduce water-tight bunding, drainage and floor-slab containment between battery rooms and IT halls so sprinkler/firefighting water from an ESS event is captured and drained rather than pooling on energised equipment (basis: Alibaba water-ingress report via DCD).
- SafetySupplement or replace water-only suppression in Li-ion battery rooms with thermal-runaway-appropriate measures (cell-level detection, gas/aerosol early suppression, dedicated cooling) to shorten the multi-day cooling operation and reduce suppression-water volume (basis: SCDF 'prolonged' cooling requirement, Straits Times).
- ProcessEstablish a pre-agreed operator re-entry and safe-shutdown protocol with SCDF so O&M engineers can perform controlled de-energisation and hardware protection earlier, rather than being unable to enter the building during the critical window (basis: DCD).
- MaintenanceInstitute and document battery-room electrical-integrity monitoring (BMS fault logging, connection/thermal inspection, state-of-charge and cell-age tracking) to close the evidentiary gap around 'an electrical issue' and enable pre-failure detection (basis: undisclosed cause / no public inspection record, Straits Times).
- DesignImprove tenant availability-zone isolation so a single-building event cannot take an entire cloud Availability Zone (and downstream Lazada/TikTok) offline via one power shutdown (basis: multi-tenant cascade, DCD/The Star).
References and provenance
- press Fire at Digital Realty data center in Singapore impacts Alibaba Cloud“Early investigations suggest an electrical issue in one of the battery rooms triggered the blaze.”https://www.datacenterdynamics.com/en/news/fire-at-digital-realty-data-center-in-singapore-impacts-alibaba-cloud/
- press Fire breaks out at data centre in Loyang; about 20 people self-evacuate“About 20 people self-evacuated before the arrival of SCDF, which deployed water jets to cool and contain the battery fire.”https://www.straitstimes.com/singapore/fire-breaks-out-at-data-centre-in-loyang-about-20-people-self-evacuate
- press Fire at Singapore data centre affects Alibaba Cloud services (The Star)“Alibaba Cloud services in Singapore, along with Lazada and ByteDance-owned TikTok, were disrupted by the data centre fire.”https://www.thestar.com.my/tech/tech-news/2024/09/11/fire-at-singapore-data-centre-affects-alibaba-cloud-services