DC Solutions · Calculator · Tier
Data center tier classification from power, cooling, network and site
Maps the infrastructure you enter to Uptime Institute Tier I–IV, TIA-942 Ratings 1–4, EN 50600 availability classes and BICSI 002, names the subsystem that limits the result and lists what reaching the next tier takes. Computed in your browser.
model weighted subsystem scores with Tier III / IV floor rules · basis Uptime Institute, TIA-942-B, EN 50600, BICSI 002 · updated 2026-10
DC Solutions → Calculator → Tier
Results
score = Σ subsystem score · weight, capped by the Tier III / IV topology rulesHeadline
Score
Framework mapping
Subsystem scores, 0–100
Gap to the next tier
Calculating.
Recommendations
Full analysis
Uncertainty: computing…
| Upgrade Action | Cost Range | Impact |
|---|
Select a region in the Regional Compliance section to see jurisdiction-specific requirements.
02 / Reference
Method
- Power
0.20 utility + 0.25 generators + 0.20 UPS + 0.10 topology + 0.10 ATS + 0.10 PDU + 0.05 fuel autonomy - Cooling
0.50 redundancy + 0.30 distribution + 0.20 type - Network
0.45 entry points + 0.30 carriers + 0.25 meet-me room - Physical
0.35 fire suppression + 0.35 access control + 0.30 monitoring - Composite
Σ subsystem score · weight, regional 50 unless set - Floor rules
score ≥ 75 needs dual feeds, N+1 generators and UPS, dual cooling paths; ≥ 90 needs 2N throughout - Tier
≥ 90 IV · ≥ 75 III · ≥ 60 II+ · ≥ 45 II · ≥ 25 I+ · else I
Computed against
Uptime Institute Tier StandardANSI/TIA-942-BEN 50600BICSI 002
Read further
Technical manual and methodologyGlossaryTIA-942 checklistCAPEX calculatorPUE calculatorDC Solutions
Estimates for education and planning, built from public industry benchmarks. Not a basis for investment, procurement or engineering decisions; confirm site-specific figures with a qualified engineer. Runs in your browser; nothing is sent to a server. Independent research; not affiliated with any current or former employer. Privacy · Terms.