Technical Manual · Reference page
Fire protection — how the page works
The fire protection page explains detection, suppression and lithium-ion battery risk in a data center: eight sections, three explorable diagrams, an incident table and a source for every number. This manual says what is on it and how it is kept correct.
▶ Open the fire protection page01 What the page is
A reference page for data center fire protection in eight numbered sections: what burns and where; detection (aspirating, spot, cross-zoned release, Li-ion off-gas); suppression (clean agent, water, EPO); lithium-ion batteries; the standard behind each number; inspection and testing intervals; real fires from 2021 to 2026; and the site’s tools, data and terms. Every number cites a row of the site’s fire datasets, the fire engine, a named standard or an incident dossier.
Three explorable diagrams carry the mechanisms: from first smoke to agent release, the sealed clean-agent room and its hold time, and the Li-ion off-gas chain. Hover a box to light the connectors it sits on; click or tap it for what it does, what feeds it and what it leads to, and a link to the section that explains it. Keyboard: Tab to a box, Enter to open, Escape to close.
Kept correct by: tools/test-figure-interact.mjs (hover, click, tap, keys and the spacing law on the page) and node tools/build-article-diagrams.mjs --check (every diagram current, zero engine warnings).
02 Linked tools and manuals
- Fire Suppression Calculator — live NFPA 2001 clean-agent sizing: agent mass/volume, cylinders, occupant-safety check, Li-ion off-gas hazard
- Fire Suppression Methodology Manual — complete equation set, constants, worked example, and NFPA 2001 references
- Fire Safety Compliance Checklist — NFPA 75/76 self-assessment checklist for data center fire-protection systems
- Fire Checklist Methodology Manual — scoring logic and clause mapping for the checklist tool
- DC Solutions Hub — broader data center design topic index
03 References & standards
- NFPA 75 (2023) — Standard for the Fire Protection of Information Technology Equipment: construction, suppression systems, detection, and housekeeping requirements for data hall spaces.
- NFPA 76 (2022) — Standard for the Fire Protection of Telecommunications Facilities: detection, suppression, and operational requirements for telecom-colocation and edge environments.
- NFPA 2001 (2022) — Clean Agent Fire Extinguishing Systems: agent mass/volume equations (halocarbon and inert), design concentrations, NOAEL/LOAEL, discharge and hold times.
- NFPA 72 (2022) — National Fire Alarm and Signaling Code: spot-detector coverage (~84 m² per detector), VESDA-class aspirating detection, alarm verification.
- NFPA 855 (2023) — Standard for the Installation of Stationary Energy Storage Systems: Li-ion battery off-gas detection at 25% LFL, ventilation requirements, suppression limitations.
- UL 9540A:2024 — Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems: off-gas LFL data and propagation test basis.
- ISO 14520 (series) — Gaseous fire-extinguishing systems: physical properties and system design (international equivalent to NFPA 2001).